Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
153
Indicators
Appendix A
Power
1734-IE4S Sensor Power
1734-IE4S Safety Analog Input Status
1734-IB8S Safety Input Status
Indicator
Description
Recommended Action
PWR
Off
No field power applied.
Apply field power.
Green
Normal condition, field power supplied and within specification.
None.
Yellow
Field power out of specification.
The module is configured to use sensor power, and either the sensor is
drawing too much current (short in the wiring or sensor), or the sensor is
not drawing any current (broken wire or sensor).
Check your connectors, wiring, and voltages.
Indicator
Description
Recommended Action
S0…S3
Off
Sensor power is not used.
None.
Green
Sensor power is used.
None.
Red
Over-current or under-current sensor power fault.
Check connectors, wiring, and power supply.
Indicator
Description
Recommended Action
0…3
(1)
Off
Safety analog input is not used or the module is being configured.
Reconfigure the channel, if desired.
Yellow
Safety analog input is configured for use and no faults exist.
None.
Red
A fault has been detected in the analog input signal path.
Check the fault code in the module using one of the data assemblies that
contains the Fault Reason. See
for details.
Check configuration, field wiring, and devices. If no problem found,
replace module.
Flashing red
A fault has been detected in the partner input signal path of a dual-input
configuration.
Check the field wiring and verify your configuration for the partner
circuit. If no problem found, replace module.
(1) Indicator behavior in Tachometer mode facilitates machine setup and troubleshooting. When the tachometer signal is below the configured OFF threshold, the indicator is off. When the tachometer signal
is above the ON threshold, the indicator is yellow. Status indicator behavior during normal operation is dependent upon the module update rate and is not intended to indicate the actual tachometer
input. When the input rate is above 30 Hz, the status indicator will be solid yellow. When the input rate is below 30 Hz, the status indicator will be flashing yellow as the signal turns on and off.
Indicator
Description
Recommended Action
0…7
Off
Safety input is off, or module is being configured.
Turn the safety input on or reconfigure the channel, if desired.
Yellow
Safety input is on.
None.
Red
A fault in the external wiring or input circuit has been detected.
Check configuration, field wiring, and devices. If no problem found,
replace module.
Flashing red
A fault in the partner input circuit of a dual-input configuration has been
detected.
Check the field wiring and verify your configuration for the partner
circuit. If no problem found, replace module.
Содержание Allen-Bradley 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Страница 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Страница 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Страница 22: ...22 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 1 POINT Guard I O Overview Notes ...
Страница 150: ...150 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 8 Replacing POINTGuard I O Modules Notes ...
Страница 180: ...180 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix C Specifications Notes ...
Страница 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Страница 190: ...190 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix E Configuration Parameters Notes ...
Страница 204: ...204 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix G History of Changes Notes ...
Страница 211: ......