188
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Appendix E
Configuration Parameters
Table 18 - Test Output Parameters
Parameter Name
(1)
Value
Description
Default
x
Test Output Mode
Not Used
An external device is not connected.
Not Used
Standard
The output is connected to a standard device.
Pulse Test
A contact output device is connected. Use in combination with a safety
input.
Power Supply
The power supply of a Safety Sensor is connected. The voltage supplied to I/
O power (V, G) is output from the test output terminal.
Muting Lamp Output (Terminal T1
or T3 only)
An indicator is connected and turned ON to detect broken lines in an
external indicator.
Test Output Fault Action
Clear OFF
Action to perform when a communication error is detected.
Clear OFF
Hold Last Data
(1) Parameters directly related to safety are marked with an x in the left column.
Table 19 - Safety Digital Output Parameters
Parameter Name
(1)
Value
Description
Default
x
Output Point Mode
Not Used
An external output devices is not connected.
Not Used
Safety
When the output is ON, the test pulse is not output (remains ON).
Safety Pulse Test
Using this function, short-circuits between output signal lines and the power
supply (positive side) and short-circuits between output signal lines can be
detected.
x
Output Point Operation Type
Single Channel
Use as single channel.
Dual-channel
Dual-channel
Use as dual-channel. When both channels are normal, outputs can be turned ON.
x
Safety Output Error Latch
Time
0…65,530 ms
(in increments of 10 ms)
Safety output errors are latched for this time.
1000 ms
(1) Parameters directly related to safety are marked with an x in the left column.
Parameter Name
Value
Description
Default
Test Output Idle State
(1)
Clear OFF or Keep Output Data
Definition of output data is in idle state.
Clear OFF
(1) Set
only
through explicit messaging. Refer to for
more information.
Table 20 - Safety Analog Input Parameters
Parameter Name
(1)
Value
Description
Default
x
Input Point Mode
Not Used
External input device is not connected.
Not Used
Safety
A solid-state safety sensor is connected.
Standard
A device that is not used in the safety loop is connected.
Range
±10V
Input voltage range.
4…20 mA
0…5V
0…10V
±5V
4…20 mA
Input current range.
0…20 mA
Tachometer
Tachometer mode.
Содержание Allen-Bradley 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Страница 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Страница 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Страница 22: ...22 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 1 POINT Guard I O Overview Notes ...
Страница 150: ...150 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 8 Replacing POINTGuard I O Modules Notes ...
Страница 180: ...180 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix C Specifications Notes ...
Страница 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Страница 190: ...190 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix E Configuration Parameters Notes ...
Страница 204: ...204 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix G History of Changes Notes ...
Страница 211: ......