Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
83
Configure the Module in a GuardLogix Controller System
Chapter 5
2.
Assign the Point Operation Type.
When you choose Equivalent or Complementary, you must also assign a
Discrepancy Time.
A discrepancy time setting of 0 ms means that the channels in a dual
configuration can be discrepant for an infinite amount of time without a
fault being declared.
For a discrepancy time setting of 0 ms, the evaluated status of the inputs
still goes to the safe state due to a ‘cycle inputs’ required condition.
However, with a 0 ms discrepancy time setting, a fault is not declared.
A ‘cycle inputs’ required condition occurs when one input terminal goes
from its normal Active->Inactive->Active state while the other input
terminal remains in its normal Active state. Even though no fault is
declared, the inputs must be cycled through the safe state before the
evaluated status of the inputs can return to the Active state. When in a
‘cycle inputs’ required condition, the logical state does not necessarily
match the voltage at the terminals.
Choose
Description
Single
Inputs are treated as single channels.
Dual-channel safety inputs can be configured as two individual single channels.
This does not affect pulse testing because it is handled on an individual channel
basis.
IMPORTANT:
Use single-channel mode when you intend to use the GuardLogix
safety application instructions.
Equivalent
Inputs are treated as a dual-channel pair. The channels must match within the
discrepancy time or an error is generated.
Complementary
Input are treated as a dual-channel pair. They must be in opposite states within
the discrepancy time or an error is generated.
IMPORTANT
Configuring discrepancy time on safety I/O modules masks input
discrepancies detected by the controller safety instructions. Status can
be read by the controller to obtain this fault information.
Содержание Allen-Bradley 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Страница 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Страница 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Страница 22: ...22 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 1 POINT Guard I O Overview Notes ...
Страница 150: ...150 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 8 Replacing POINTGuard I O Modules Notes ...
Страница 180: ...180 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix C Specifications Notes ...
Страница 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Страница 190: ...190 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix E Configuration Parameters Notes ...
Страница 204: ...204 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix G History of Changes Notes ...
Страница 211: ......