Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
113
Configure the Module for a SmartGuard Controller
Chapter 6
6.
Double-click Test Output Points to edit their configuration.
7.
Click Apply and OK.
Configure Digital Safety Outputs
1.
Double-click each group of Outputs Points to display the parameters for
editing.
2.
Double-click Output Error Latch Time to change from the default value
(1000ms), if desired.
Parameter Name
Value
Description
Default
Test Output Mode
Not Used
An external device is not connected.
Not Used
Standard
The output is connected to a standard device.
Pulse Test
A contact output device is connected. Use in combination with a safety input.
Power Supply
The power supply of a Safety Sensor is connected. The voltage supplied to I/O power (V, G) is
output from the test output terminal.
Muting Lamp Output
(Terminal T1 or T3 only)
An indicator is connected and turned ON to detect broken lines in an external indicator.
Parameter Name
Value
Description
Default
Output Point Mode
Not Used
An external output devices is not connected.
Not Used
Safety
When the output is ON, the test pulse is not output (remains ON).
Safety Pulse Test
Using this function, short-circuits between output signal lines and the power supply (positive side)
and short-circuits between output signal lines can be detected.
Output Point Operation
Type
Single Channel
Use as single channel.
Dual-channel
Dual-channel
Use as dual-channel. When both channels are normal, outputs can be turned ON.
Safety Output Error Latch
Time
0…65,530 ms
(in 10 ms increments)
Safety output errors are latched for this time.
1000 ms
Содержание Allen-Bradley 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Страница 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Страница 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Страница 22: ...22 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 1 POINT Guard I O Overview Notes ...
Страница 150: ...150 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 8 Replacing POINTGuard I O Modules Notes ...
Страница 180: ...180 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix C Specifications Notes ...
Страница 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Страница 190: ...190 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix E Configuration Parameters Notes ...
Страница 204: ...204 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix G History of Changes Notes ...
Страница 211: ......