Installation
Operating_Manual_Fan_KXE_04_en.docx
42 / 128
Tightening torque [Nm] *
M 24
144
M 30
290
* For stone bolt in accordance with DIN 529 form B,
property class 4.6
If insulation for the fan or a provision for on-site insulation is
included within the scope of delivery, refer to the following
section.
There are three variants:
- Insulation realised entirely at the factory
- Insulation not entirely realised at the factory (insulation
must be finalised at the construction site)
- Provision from the factory for implementation of
complete insulation at the construction site
The variant of insulation applicable for your respective
installation is specified at the following sources:
- On the fan data sheet
- On the general drawing of the fan
NOTICE!
Our separate insulation requirement is available upon
request in the event that insulation work must be
performed on site.
Perform all insulation work prior to mounting the fan
wherever insulation work will be rendered impossible
following mounting due to insufficient space or other
impairments.
7.5 Insulation of the fan
Table 7-3
Tightening torques for stone bolts