Measures prior to commissioning
Operating_Manual_Fan_KXE_04_en.docx
45 / 128
NOTICE!
Check radial offset with a straightedge, check
angular offset with a feeler gauge.
NOTICE!
Refer also to the separate instructions of the coupling
manufacturer.
Coupling configuration in accordance with ATEX (optional):
If the coupling is intended for use in potentially explosive
environments pursuant to Directive 2014/34/EU (ATEX),
corresponding identification is provided in this regard.
Regard the type of configuration when ordering spare parts.
Specifications in the table are general reference values for
the maximum permissible offsets.
An alignment precision of ≤ 0.1 mm is to be targeted for all
three offsets with extremely high demands regarding the
quiet running and for impeller speeds > 3,000 rpm.