Measures prior to commissioning
Operating_Manual_Fan_KXE_04_en.docx
54 / 128
Re-lubrication device for the bearing:
Regular re-lubrication by the maintenance personnel is no
longer applicable when using automatic re-lubrication
devices (grease injectors).
Set the dispensing period at the grease injector in
accordance with respective size of the bearing in accordance
with Table 8-3
Specifications for the respective bearing can be obtained
from the following sources:
- On the corresponding information plate on the fan
- On the fan data sheet
- In the spare parts list
The dispensing periods were determined taking the following
conditions into account:
- Grease injector with 250 grams of grease
- Fan operation of 80 operating hours per week
Setting of the dispensing periods can be modified if the
actual conditions deviate from these conditions.
WARNING
Fan shaft bearings!
Damage to the bearing as a result of insufficient lubrication.
→ Ensure sufficient lubrication of the bearings at all times
with the measures specified as follows:
Activate the automatic re-lubrication device
(grease injector).
Ensure correct connection of the lubricating
line.
Inspect the lubricating line for blockages.
Replace used or faulty re-lubrication devices
(grease injectors).
8.5.1 Bearings