Commissioning DFA 127
13
102-127108955
V1.1
49/ 102
Changing addresses
The address must be changed if a wrong position has been assigned by mistake to a sensor
while the system has already been activated. The correct procedure is explained in the fol-
lowing example:
Example of wrong addressing:
Inside-RAD 290 → correct addressed as AKI 1
Outside-RAD 290 → wrong addressed as AKI 2
Consequently the operating mode "One-Way" does not work. Addressing must be modified.
Procedure:
Disconnect Outside-RAD 290 from bus
Address Inside-RAD 290 as AKA 1
Connect sensor to bus again
Deactivate no longer existing sensor AKI 2 with FPC in menu SERVICE STG / PARAME-
TER / CAN-BUS
Newly addressed sensor AKA 1 is automatically detected and activated.
Deactivating / reactivating bus components (replacing faulty sensors)
In the event of a sensor being faulty and must be replaced, the defective unit must only be
deactivated if a replacement is not immediately available.
Otherwise, the replacement must be addressed in the same way and then be connected to
the bus. Subsequently, a learning cycle must be performed for this sensor.
Procedure for deactivating:
▪ Disconnect defective or superfluous sensor from bus.
▪ Select this sensor with FPC in menu SERVICE STG / PARAMETER / CAN-BUS and de-
activate it.
13.2.5
13.2.6
Содержание DFA 127
Страница 31: ...Assembly dimension diagrams 10 102 127108955 V1 1 31 102 Dimension diagram 2 for standard arms 10 2 ...
Страница 98: ...Drawings 25 102 127108955 V1 1 98 102 Drawings Cable layout 25 25 1 ...
Страница 99: ...Drawings 25 102 127108955 V1 1 99 102 ...
Страница 100: ...Drawings 25 102 127108955 V1 1 100 102 Wiring diagram 25 2 ...
Страница 101: ...Drawings 25 102 127108955 V1 1 101 102 ...
Страница 102: ...Drawings 25 102 127108955 V1 1 102 102 ...