Configurations
16
102-127108955
V1.1
77/ 102
→ Locked
The output signal shows whether the door is locked.
Output 0 V = door not locked.
Output 24 V = door closed and locked.
▪ The output is only set correctly for locking by VAK
signal.
→ Closed
This output signal shows whether the door is closed.
Output 0 V = door not closed.
Output 24 V = door closed.
▪ The output may switch with a slight delay, i.e. when
closing only after the pressing phase and, when ope-
ning by hand, not before the door has opened by ap-
prox. 10 mm.
INPUT/OUTPUT --> FEM1
→ FEM type
This parameter assigns the configurable input and output sig-
nals of the FEM1 to application-compatible default values.
→ Basic
X All input and output signals are deactivated.
Configuration for interlock operation.
▪ It is possible to operate the system with sensors be-
tween the doors or without sensors with interlock se-
quential control.
Parameter
Default value
Input → AUX10_IN
S_AUS
Input → AUX11_IN
SEA
Input → AUX12_IN
SFS_IN
Output → AUX10_OUT
SAA
Output → AUX11_OUT
SAMP
→ Interlock
Output → AUX12_OUT
SFS_OUT
→ AUX10_IN
Configurable input signal for FEM1
Connector J1, terminals 64 & 65
Floating, optically disconnected 24V input
→ Disabled
X
→ S_AUS
Interlock control disabled.
▪ Both doors open at the same time by activation at
one side. SIS is active and stops the respective door.
Содержание DFA 127
Страница 31: ...Assembly dimension diagrams 10 102 127108955 V1 1 31 102 Dimension diagram 2 for standard arms 10 2 ...
Страница 98: ...Drawings 25 102 127108955 V1 1 98 102 Drawings Cable layout 25 25 1 ...
Страница 99: ...Drawings 25 102 127108955 V1 1 99 102 ...
Страница 100: ...Drawings 25 102 127108955 V1 1 100 102 Wiring diagram 25 2 ...
Страница 101: ...Drawings 25 102 127108955 V1 1 101 102 ...
Страница 102: ...Drawings 25 102 127108955 V1 1 102 102 ...