Configurations
16
102-127108955
V1.1
64/ 102
→ Mech. end stop
▪ This feature can be configured if the option MS Mech.
door stop (102-127808234) is built-in or a door stop is
installed.
→ Disabled
X Function deactivated
→ Active
The door is held more firmly in the open position.
▪ Recommended for wind load or pressure fluctuations.
DOOR SYSTEM
→ Fire alarm system
Specific adaptation to the requirements of the EN standards
for fire protection systems.
→ Disabled
X Function disabled
→ Active
Fulfilment of the requirements of the EN standards for fire pro-
tection systems. The door starts to move with less force.
→ Control
In operation, this happens automatically. With the FPC 902, a
control mode can be imposed upon the drive for simulation
purposes or to divide a master / slave system.
→ Individual control
X Single door, jumper J14 is in position M1
→ Master control
Master of a master / slave system, jumper J14 is in position
M1
→ Slave control
Slave of a master / slave system, jumper J14 is in position S1
→ Master interlock
Master with interlock control, jumper J14 is in position M2
→ Slave interlock
Slave with interlock control, jumper J14 is in position S2
Содержание DFA 127
Страница 31: ...Assembly dimension diagrams 10 102 127108955 V1 1 31 102 Dimension diagram 2 for standard arms 10 2 ...
Страница 98: ...Drawings 25 102 127108955 V1 1 98 102 Drawings Cable layout 25 25 1 ...
Страница 99: ...Drawings 25 102 127108955 V1 1 99 102 ...
Страница 100: ...Drawings 25 102 127108955 V1 1 100 102 Wiring diagram 25 2 ...
Страница 101: ...Drawings 25 102 127108955 V1 1 101 102 ...
Страница 102: ...Drawings 25 102 127108955 V1 1 102 102 ...