Configurations
16
102-127108955
V1.1
80/ 102
→ Alarm display
In this menu, some error messages can be adapted to special
requirements.
▪ Display for AKI/AKA/SSK or SIO/SIS
If the alarm output has been configured, it switches
after expiry of the set time.
→ Time activation
18 Triggering signals activated for a relatively long time (AKI,
AKA, SSK) are displayed with an error message.
0 = no error message
1..40 = display an error message after 5..200 seconds
→ Time safety
18 Safety signals activated for a relatively long time (SIO, SIS)
are displayed with an error message.
0 = no error message
1..40 = display an error message after 5..200 seconds
Special remarks
If the value 2 (BDE-M/4-positions) has been programmed and an external mechanical BDE
(BDE-M) has been connected, the inputs (BDE1, BDE2) will be interpreted in a different
manner. On the circuit board in the mounting set, BDI-M DFA 127 (102-127808232) is
equipped with clamps that permit the external adjustment of the operation mode according
to the table below.
Terminal connections on the circuit board in the mounting set BDI-M:
Input/output on
STG DFA 127
Clamps on
STG DFA 127
Clamp marking on BDI-
M
BDE 1
J7/1
1
BDE 2
J7/2
2
+ 24 V
J7/3
3
NOTICE
If using the circuit board on the side cover, only the RESET button and the status
signal remain in function.
16.3
Содержание DFA 127
Страница 31: ...Assembly dimension diagrams 10 102 127108955 V1 1 31 102 Dimension diagram 2 for standard arms 10 2 ...
Страница 98: ...Drawings 25 102 127108955 V1 1 98 102 Drawings Cable layout 25 25 1 ...
Страница 99: ...Drawings 25 102 127108955 V1 1 99 102 ...
Страница 100: ...Drawings 25 102 127108955 V1 1 100 102 Wiring diagram 25 2 ...
Страница 101: ...Drawings 25 102 127108955 V1 1 101 102 ...
Страница 102: ...Drawings 25 102 127108955 V1 1 102 102 ...