ESPLXD-ET Controller
Connecting Power to the Controller
Connect Ground Wire
The ESPLXD-ET controller is equipped with built-in electrical surge
protection. For this system to function, you must properly ground the
controller.
b
c
WARNING:
The ground wire MUST be connected to provide
electrical surge protection. Connect the controller to the
grounding grid using at least a #8 AWG (10 mm) or #10 AWG
(6 mm) bare copper wire. The wires should be as short and as
straight as possible. You will void the controller warranty if you do
not ground the controller to a minimum resistance of five ohms.
Connect Power Source
The ESPLXD-ET controller has an internal transformer that reduces
supply voltage (120 VAC in U.S. models; 230 VAC in international
models; 240 VAC in Australian models) to 24 VAC to operate the
decoders connected to the controller. You will need to connect power
supply wires to the transformer’s three wires.
b
c
WARNING:
Electric shock can cause severe injury or death. Make
sure power supply is turned OFF before connecting power wires.
b
c
WARNING:
All electrical connections and wiring runs must be
made according to local building codes.
A
With the front panel removed, locate the transformer wiring
compartment in the lower left corner of the controller cabinet.
Remove the screw on the right-hand side and pull the cover off to
expose the wiring compartment.
1
Wiring Connections
120 VAC (US)
230 VAC (International)
Black supply wire (hot) to the black
transformer wire
Black supply wire (hot) to the black
transformer wire
White supply wire (neutral) to the
white transformer wire
Blue supply wire (neutral) to the
blue transformer wire
Green supply wire (ground) to the
green transformer wire
Green-with-yellow-stripe supply
wire (ground) to the green-with-
yellow-stripe transformer wire