PT113
Instruction Manual
6
Model specific specifications
PT113MB
Protocols and Data Rate
RS485 1200 to 5700 baud, 8N1 / 7O1 / 7E1. Continuous, Command or BSI,
Modbus RTU (H-L, L-H) on RS-485.
Maximum stations
Up to 31 units per segment.
Response Speed
< 4mS response delay from read/write commands.
PT113EN
Protocol and Data Rate
TCP/IP Continuous, BSI or Command and Modbus TCP (H-L, L-H), 10
Mbit/s, half duplex.
TCP/IP settings
Manual IP assigned during programming.
Installation
Switched Ethernet transmission with shielded twisted pair cables and RJ-45
connectors.
Response Speed
< 4mS response delay from read/write commands.
PT113PB
Protocol and Data Rate
PROFIBUS DP V1. 9.6 kbit/s to 12 Mbit/s automatic baud rate detection,
PLC setup
Generic GSD-file provided.
Topology
Media dependent, RS-485 segmented line without stubs.
Installation
Shielded twisted pair cable, line length depending on physical media and
transmission speed.
Maximum stations
Up to 32 stations per segment, up to 126 stations per network.
Isolation
Galvanically isolated bus electronics.
Response Speed
< 4mS response delay from read/write commands.
PT113PN
Data Rate
100 Mbit/s, full duplex
PLC setup
Generic GSDML-file provided
TCP/IP settings
DHCP or manual IP assignment during set up programming.
Device identity customization.
Topology
Line, Bus, Star or Tree topology depending on physical media.
Installation
Switched Ethernet transmission with shielded twisted pair cables and RJ-45
connectors.
Isolation
Galvanically isolated bus electronics.
Response Speed
< 4mS response delay from read/write commands.
PT113EI
Data Rate
10 or 100 Mbit/s, full duplex
PLC setup
Generic EDS-file provided
DLR (Device Level Ring)
Available
TCP/IP settings
DHCP or manual IP assignment with EtherX software.
Device identity customization.
Topology
Line, Bus, Star or Tree topology depending on physical media.
Installation
Switched Ethernet transmission with shielded twisted pair cables and RJ-45
connectors.
Isolation
Galvanically isolated bus electronics.
Response Speed
< 4mS response delay from read/write commands.
PT113CO
Data Rate
10 kbit/s – 1 Mbit/s (selectable) kbit/s
PLC setup
Generic ESD-file provided
Topology
Line with Trunk line, Drop line structure and termination at both ends. Line
length 25 – 500 metres, dependent upon baud rate.
Installation
2 wires shielded twisted pair cable. Alternatively 4 wire with 24 Volt power
over the bus.
Maximum stations
Up to 127 stations per network.
Isolation
Galvanically isolated bus electronics
Response Speed
< 4mS response delay from read/write commands.