Identcode
Identcode Measuring/Control Station DULCOTROL
®
Cooling Water –
Three Measured Variables
CWCA Measured variable
LCP0 1. Conductivity / 2. free chlorine / 3. pH (at pH-value < 8.0)
LCP1 1. Conductivity / 2. free chlorine / 3. pH (at pH value > 8.0 or unstable)
LGP0 1. Conductivity / 2. total chlorine (free+combined chlorine) / 3. pH
LBP0 1. Conductivity / 2. bromine organic (e.g. BCDMH, Stabrex) / 3. pH
LBP1 1. Conductivity / 2. free bromine (HOBr) / 3. pH
LDP0 1. Conductivity / 2. chlorine dioxide (with temperature as correction variable) / 3. pH
LZP0 1. Conductivity / 2. ozone / 3. pH
LHP0 1. Conductivity / 2. hydrogen peroxide / 3. pH
Water to be measured
1
Cooling water
Usage category
0
All measured variables measurable (Lxxx: desalinate, blow down)
4
1st measured variable = conductivity: Demineralisation, 2nd +3rd measured variable only measurable
5
2nd measured variable two-way controllable, 1st measured variable = conductivity: desalinate, blow down, 3rd measured
variable only measurable
6
1st measured variable = conductivity: desalinate (blow down), 2nd + 3rd measured variable one-way controllable with two-
channel controller D2C (only LCP0/LGP0/LDP0)
7
1st measured variable = conductivity: desalinate (blow down), 2nd + 3rd measured variable two-way controllable
9
All measured variables two-way controllable
Power supply
A
230 V, 50/60 Hz
C
115 V, 50/60 Hz
Sensor equipment
0
With sensors
1
Without sensors
Version
0
With ProMinent logo
Sample water treatments
0
None
1
With filter
2
With peristaltic pump
3
With filter and peristaltic pump
Accessories
0
None
1
With pressure reducer
2
With heat exchanger
3
With sample water pump
4
With pressure reducer and heat exchanger
6
With heat exchanger and sample water pump
Language
DE
German
EN
English
FR
French
IT
Italian
NL
Dutch
ES
Spanish, not for H in LHP0
PL
Polish, not for H in LHP0
SV
Swedish, not for H in LHP0
HU
Hungarian, not for H in LHP0
PT
Portuguese, not for H in LHP0
CS
Czech, not for H in LHP0
Approvals
1
CE
BA_DR_002_02_09_GB_Cooling.indd 10