Operation
Note
text
Symbol
Effect
Alarm with ack- Remarks
Remedy
on metering on control
nowledgement
Stop button
Stop button
none
Stop no
Start
device
Pause contact
Pause
none
Stop
yes, may be
delay time td adjustable,
Deactivate interval
deactivated display elapsing “td”
deactivate delay time „td“
Fault measuring water
Fault measuring water
none
Stop
yes
Function
switchable
High chlorination
High chlorination
max. frequency
Stop
no
Function switchable
Base load chlorine
Base load chlorine
frequency
no Function
switchable
adjustable
Electronic fault
EEPROM defective
none
Stop
yes
Send in device
8.9.3
DULCOMETER
®
D2C, DULCOTEST
®
CTE Sensors for Total Chlorine and
DULCOTEST
®
Sensors PHEP or PHER for pH, Troubleshooting
Controller
Fault
Fault
text
Symbol
Effect
Alarm with ack- Remarks
Remedy
on metering on control
nowledgement
Measured value 1
Signal exceeded/
pH-input
Basic load
Stop
yes
3 mA>Signal>23 mA
Check sensor, transducer and
drops below value
-499 mV>Signal>499 mV
cable connection
Calibration with error
pH calibration defect
Basic load
Stop
no
Check sensor, replace if
necessary,
recalibrate
if
necessary
Measured value 2
Signal exceeded/
Cl-input
Basic load
Stop
no
3 mA>Signal>23 mA
Check sensor, transducer and
drops below value
cable connection
Calibration with error
Cl calibration defect
Basic load
Stop
no
Check sensor, clean or
replace
if
necessary,
recalibrate
if
necessary
Limit transgression
pH-limit value 1
none
Stop yes
Function
may
after checkout time
Cl-limit value 2
be
deactivated
Correcting variable
Signal exceeded/
°C-input
Basic load
Stop
yes
Signal ~ 100
Ω
or
drops below value
~138.5
Ω
pH/Chlorine