Calibration of the Chlorine Sensor (Continuation)
The calibration (slope calibration) of the chlorine sensor uses the DPD method. When starting
cali bra tion, the frozen measuring value is proposed; this value may be adjusted to the meas-
ured DPD value using the Up and Down buttons. A calibration will only be possible if the
DPD value is
≥
2% of the measuring range. During calibration, control function and metering are
maintained. After successful calibration, all fault determinations relating to the measuring value
are started again.
With a measuring range adjusted to 0 - 0.5 ppm, the zero point may be calibrated in the entire
operating menu in addition to the slope. The zero point calibration should be performed under
realistic condition with chlorine-free water. In this case, control will be stopped and metering will
be reduced to the set base load.
The output 0/4...20 mA (measuring value) will be frozen.
IMPORTANT
The measuring range of the chlorine sensor must correspond to the adjusted measuring
range of the DULCOMETER
®
D2C (factory setting 0 - 2.00 ppm). A possible alteration of the
measuring range must be done prior to calibration. If the measuring range is altered, all
settings are reset to the factory settings.
pH/Chlorine
Possible
values
Initial value
Increment
Lower value
Upper value
Remarks
DPD-value Measured value 0.01 ppm
0 ppm
20 ppm
Zero point Measured value –
–
–
(mA)
Error message
Condition
Remarks
Calibration Cl not possible!
Cl slope too low
Repeat calibration
Sensor slope too low
(<25% of standard slope)
Calibration Cl not possible!
Cl slope too high
Repeat calibration
Sensor slope too high
(>300% of standard slope)
DPD value too low!
DPD <2 % of measuring range Repeat calibration after
DPD > x.xx ppm
addition of chlorine
Zero point too high
Sensor signal >5 mA
Repeat calibration in
chlorine-free
water
Zero point too low
Sensor signal <3 mA
Check sensor connection
replace sensor, if necessary
calibration
end?
calibration Cl
2
zero p.: 4.00 mA
slope:
6.00 mA/ppm
only with measuring
range 0,5 ppm
calibration Cl
2
zero p.: 4.00 mA
slope:
6 mA/ppm
calibration Cl
2
zero point:
0.45 ppm
calibration Cl
2
zero point
value take over?
4.01 mA
calibration Cl
2
DPD-value
0.45 ppm
calibration Cl
2
DPD-value:
0.45 ppm