Deviating Settings of the Controller
9.2
Setting of the Pause Contact for Flow Monitoring
Flow
Monitoring
IMPORTANT
The
fl ow of the sample water must be monitored because varying or faulty readings may
result in case of insuffi cient or no fl ow!
For a DULCOMETER
®
D1C as single unit, the fl ow monitoring is designed as make contact as
standard (default). A cable break cannot be monitored.
For the DULCOMETER
®
D1C of the measuring/control stations DULCOTROL
®
cooling water, this
fl ow monitoring is factory-designed as break contact. In case of cable break or if a certain
minimum fl ow rate to be set is andershot, an alarm is triggered. The controlling goes to “Pause”
and the display of the controller D1C shows “Pause”.
The minimum fl ow rate value can be adjusted by moving the limit value contact at the fl ow meter
to the top and bottom, resp.
For all types of the fl ow monitoring, the alarm relay is activated:
alarm relay
active
Access to all setting menus can be blocked with an access code !
general setting
information
identcode: D1CA
DxFxxxxxxxxxx
software version
D1C-C1 FW-5.00
access c.:
5000
operating menu:
= english
= complete
- pause normal
- active... open
- alarm on
- td: 0 min