Measured variable
Sample
Default
Used sensor Readjustment of the
water
sensor
type
sensor type for D1C to
type
for
D1C
Inductive conductivity 1
ICT 1
ICT 1
Not required
Deviating Settings of the Controller
9
Settings of the Controllers D1C/D2C Deviating from the
Data in the D1C/D2C Operating Instructions
(to be observed during repairs)
9.1
Deviating Measuring Ranges
The D1C controllers of the measuring/control stations DULCOTROL
®
drinking water/F&B are
delivered to the customer ready for operation. Settings for the measuring ranges are not required.
For Repair or Replacement
For many amperometric sensors, the measuring range deviates from the standard measuring
range (default value) of the controller. When repairing or replacing the controller these values
may have to be corrected or adjusted. For this purpose, the controller’s measuring range values,
which are documented in the individual operating instructions, must be checked and modifi ed,
if required.
To do so, the respective controller must be adjusted to the measuring range of the sensor. The
procedure is described in the individual operating instructions for the controller. The respective
setting values with regard to controller/sensor are listed in the table below.
For the measured variable “Inductive conductivity” it may be required to adjust the sensor type
when repairing or replacing the controller D1C.
The exact procedure is described in the individual operating instructions for the controller. For an
exact assignment and designation of the individual operating instructions, please see the list
“further applicable documents” in the annex of the present instructions.
Measured variable Default measuring
Sensor type
Readjustment of the
range D1C
measuring range to
Bromine organic
10 ppm
BRE 1 - mA - 0,5 ppm
Not required
Free bromine
BRE 2 - mA - 2 ppm
2 ppm
Free chlorine
2 ppm
CLE 3 - mA - 0,5 ppm
0.5 ppm
Chlorine dioxide
2 ppm
CDR 1 - mA - 0.5 ppm
0.5 ppm
Total chlorine
2 ppm
CTE 1 - mA - 0.5 ppm
0.5 ppm
Hydrogen peroxide 200 ppm
PER 1 - mA - 200 ppm
Not required
Ozone
2 ppm
OZE 3 - mA - 2 ppm
Not required