SECTION 06B: ELECTRICAL
13
Connector C426 corroded
Circuit 292 open
FMI 6
Current
above normal
Output A52 J1:2
internal software fuse
active for overcurrent
Radiator fan
clutch Mo2 not
working on
speed 2
A52 module failure
Connector C91 corroded
Connector C426 corroded
Circuit 292 shorted to battery
MID 188 PSID # 70 Ent Close Out (A36 JB:17)
Type of
fault:
FMI
Description:
Fault Condition:
Possible
Symptoms:
Possible Causes:
FMI 3
Shorted High Voltage above
normal on A36 JB:17
Entrance door
cannot be
opened
A36 module failure
Sw34 failure
Connector C6 corroded
Circuit 49 shorted to battery
FMI 4
Shorted Low
Voltage below normal
on A36 JB:17
Entrance door
cannot be closed
with switch
A36 module failure
Sw34 failure
Connector C6 corroded
Circuit 49 shorted to ground
MID 188 PSID # 63 Ent Close Sens (A47 J1:10)
Type of
fault:
FMI
Description:
Fault Condition:
Possible
Symptoms:
Possible Causes:
FMI 3
Shorted High Voltage above
normal on A47 J1:10
Entrance door
cannot be
opened
A47 module failure
Se76 failure
Connector CXC1 corroded
Circuit 3 shorted to battery
FMI 4
Shorted Low
Voltage below normal
on A47 J1:10
Entrance door
cannot be
closed with
switch
A47 module failure
Se76 failure
Connector CXC1 corroded
Circuit 3 shorted to ground
MID 188 PSID # 65 Ent Close Sol (A47 J1:6)
Type of
fault:
FMI
Description:
Fault Condition:
Possible
Symptoms:
Possible Causes:
FMI 3
Shorted High Voltage present on
output A47 J1:6 but
output not active
Close Solenoid
Valve So6
always ON -
Entrance door
cannot be
opened
A47 module failure
Close solenoid valve So6
failure
Circuit 49A shorted to battery
FMI 4
Shorted Low
Output A47 J1:6
shorted to ground
Entrance door
cannot be
closed with
switch
A47 module failure
Close solenoid valve So6
failure
Circuit 49A shorted to ground
FMI 5
Open Circuit
A47 module does not
detect Close
Solenoid Valve So6
Entrance door
cannot be
closed with
switch
A47 module failure
Close solenoid valve So6 open
Circuit 49A open
FMI 6
Current
above normal
Output A47 J1:6
internal software fuse
active for overcurrent
Entrance door
cannot be
closed with
switch
A47 module failure
Circuit 49A shorted to ground
Close solenoid valve So6
shorted to ground
Содержание X3-45 2016
Страница 4: ......
Страница 16: ...Section 00 GENERAL INFORMATION PA1593 12 FIGURE 12 METRIC US STANDARD CONVERSION TABLE 00005...
Страница 17: ...Section 00 GENERAL INFORMATION 13 PA1593 FIGURE 13 CONVERSION CHART 00006...
Страница 18: ......
Страница 26: ......
Страница 58: ......
Страница 72: ...Section 04 EXHAUST AND AFTERTREATMENT SYSTEM PA1593 14 7 TORQUE SPECIFICATIONS...
Страница 73: ...SECTION 04 EXHAUST AND AFTERTREATMENT SYSTEM PA1593 15...
Страница 74: ...Section 04 EXHAUST AND AFTERTREATMENT SYSTEM PA1593 16...
Страница 76: ......
Страница 96: ......
Страница 134: ......
Страница 176: ...SECTION 06B ELECTRICAL 38 overcurrent working Circuit 306 shorted to ground...
Страница 180: ......
Страница 202: ......
Страница 205: ...Section 09 PROPELLER SHAFT PA1593 3 FIGURE 1 PROPELLER SHAFT ASSEMBLY 09002...
Страница 256: ......
Страница 268: ......
Страница 295: ...SECTION 16 SUSPENSION PA1593 9 2 5 TORQUE SPECIFICATIONS...
Страница 296: ...Section 16 SUSPENSION PA1593 10...
Страница 297: ...Section 16 SUSPENSION PA1593 11...
Страница 314: ......
Страница 364: ...Section 18 BODY PA1593 50 6 8 BODY PANEL AND WINDOW SPACING FIGURE 45 BODY PANEL AND WINDOW SPACING TYPICAL 18631...
Страница 380: ......
Страница 388: ......
Страница 413: ...Section 22 HEATING AND AIR CONDITIONING PA1593 15 FIGURE 18 REFRIGERANT CIRCUIT CENTRAL SYSTEM...
Страница 433: ...Section 22 HEATING AND AIR CONDITIONING PA1593 35 FIGURE 36 CENTRAL HEATING SYSTEM COMPONENTS...