58
PA8506-V
|
VES Compact System
PA8500-VES | Voice Evacuation System
System Manual | 2014
UK
For.zones.with.a.current.ALERT.message.activated.manually,.it.is.possible.to.activate.the.Evacuation.message.by.pressing.the.EVAC.key.
directly.
For.zones.with.a.current.EVAC.message.activated.manually,.it.is.only.possible.to.send.out.an.Alert.message,.which.has.a.lower.priority,.after.
RESETTING.the.zone,.as.indicated.under.point.8.9.4.
• Exiting manual management of an emergency
Upon.completion.of.the.procedure.for.managing.the.Manual.Emergency,.press.the.red.EMERGENCY.key,.which.will.extinguish,.and:
. -.
if no activation from external peripheral units connected to the “Control Input” contacts are activated
,.the.system.will.return.automatically.to.
the.idle.condition,.displaying.the.MUSIC.menu..The.ALARM.LED.will.remain.extinguished.to.indicate.that.the.VOICE.ALARM.is.not.active.
. -.
If there are any current activations from external peripheral units connected to a “Control Input” contact
,. the. system. will. return. to. the.
Automatic.Emergency.condition,.displaying.the.INPUT.ALARM.STATUS.menu..Broadcasting.of.the.emergency.messages.will.resume,.on.
the.basis.of.the.programming.of.the.activated.inputs.and.with.–.if.appropriate.–.the.ALARM.LED.illuminated.to.indicate.an.active.VOICE.
ALARM.
8.9.4 Manual resetting of the alarms
It.is.possible.to.carry.out.general.or.partial.RESETTING.of.the.alarm.messages,.based.on.whether.the.zones.are.selected.or.whether.they.have.
alarms.in.progress..
• GENErAL resetting of current messages
On.accessing.the.Emergency.panel.for.the.first.time,.the.zones.will.already.all.be.selected..As.an.alternative,.it.is.possible.to.place.the.zones.in.
a.condition.of.general.selection,.as.indicated.under.point.8.9.5.
. .
•..Press.the.RESET.key.
The.message.being.played.out.to.the.zones.will.be.reset,.the.status.labels.of.the.zones.will.become.empty.and.the.zones.will.all.be.in.a.selected.
condition..The.ALARM.LED.will.extinguish.to.indicate.that.the.“Alarm.Condition”.is.de-activated.
• PArTIAL resetting of the current messages
Partial.resetting.is.permitted.only.for.zones.with.messages.playing.out.that.have.been.activated.manually.
. .
•..Select.the.zones.to.be.reset
. .
•..Press.the.RESET.key
In.the.zones.that.have.been.reset,.the.message.that.was.activated.manually.will.be.de-activated.and,.if.appropriate,.the.message.that.was.playing.
out.due.to.an.earlier.automatic.activation.will.be.resumed...The.other.zones,.that.have.not.been.reset,.will.continue.to.broadcast.the.current.
message..The.system.will.switch.the.zones.to.general.selection.
Note
:.If.the.RESET.is.carried.out.without.selecting.the.zones.first,.the.messages.to.all.the.zones.will.be.reset.and,.for.about.10.seconds,.only.
the.zones.for.which.messages.had.been.activated.manually.will.continue.to.be.selected..Then.the.general.selection.of.all.the.zones.will.be.
restored
Note
:.Following.broadcasting.to.all.zones.of.an.alarm.message.or.partial.RESETTING.of.some.zones,.the.labels.may.all.“STOP.FLASHING”..
The.condition.of.the.zones.corresponds,.however,.to.a.state.of.general.selection,.equivalent.to.indicating.the.zones.as.“ALL.FLASHING”..
Management.of.a.Manual.Emergency.does.not.include,.therefore,.a.condition.of.“All.zones.not.selected”.
8.9.5 Selecting/unselecting the emergency areas
Press.the.numerical.keys.of.the.zones.in.question.in.order.to.select/unselect.a.zone.or.group.of.zones.as.required,.according.to.the.following.
indications:.
•.Zone.label.flashing.=.zone.selected
•.Zone.label.not.flashing.=.zone.not.selected
•.Zone.labels.all.flashing.=.all.zones.selected
•.NO.zone.labels.flashing.=.all.zones.selected.(see.note).
•.The.zones.with.status.labels.indicating.DIS.cannot.be.selected.
The.condition.of.general.selection.of.all.the.zones.is.also.indicated.by.the.text.on.the.display,.reading:
. “PTT,.EVAC.or.ALERT.
for general call
,...”
while.during.the.stage.of.selection.of.a.group.of.zones.the.display.will.read:
. “PTT,.EVAC.or.ALERT.
for zone(s) call
...”