6. OPErATING CONdITIONS ANd TErMINOLOGy
6.1 GENErAL dEFINITIONS
Following.is.a.list.of.the.signalling.modes.of.the.operating.conditions.of.the.system.and.of.definitions.used.in.the.rest.of.the.manual,.completed.
by.indications.of.a.general.nature:
6.1.1 Signalling of operating conditions
The.PA8506-V.system.is.structured.to.signal.the.different.operating.conditions.on.the.basis.of.the.following.definitions:
“Quiescent condition” (ALArM – FAULT – dIS – SyS LEds extinguished)
Normal.operating.condition,.with.no.current.failures.or.emergencies..This.status.enables.the.sources.of.music.and.voice.to.be.managed.for.
service.announcements.
“Alarm Condition” (ALArM LEd illuminated)
This.operating.condition.signals.the.current.presence.of.at.least.one.alarm.signal,.either.pre-recorded.or.live,.on.at.least.one.output.zone..The.
“Alarm.Condition”.can.be.activated.in.the.form.of.an.Automatic.Emergency.from.an.external.peripheral.unit.connected.to.the.Control.Inputs.or.of.
a.Manual.Emergency.through.an.authorised.operator..During.an.“Alarm.Condition”,.the.functions.of.the.music.sources.and.of.the.voice.services.
referred.to.the.quiescent.condition.are.not.operational..In.a.12-zone.system.with.two.interconnected.PA8506-V.units,.generally.speaking.an.
“Alarm.Status”.is.activated.on.both.units,.regardless.of.which.output.zone.has.triggered.the.alarm.
“Fault warning condition” (FAULT Led illuminated)
This.operating.condition.signals.the.presence.of.at.least.one.current.failure,.detected.by.the.internal.diagnostics.system..It.is.accompanied.by.
an.acoustic.signal.(buzzer).indicating.the.failure..Depending.on.the.causes.of.the.failure,.the.system.may.in.any.case.perform.the.functions.
relating.to.the.“Quiescent”.and.“Alarm”.conditions.
“Faulty status” (FAULT LEd flashing)
In.a.12-zone.system.with.two.interconnected.PA8506-V.units,.it.signals.the.presence.of.at.least.one.current.failure.referred.to.the.other.remote.
PA8506-V.unit.or.to.the.items.connected.to.it.and.subjected.to.monitoring..It.is.accompanied.by.an.acoustic.fault.alarm.(buzzer)..If.the.causes.
of.the.fault.enable.this,.the.system.may.in.any.case.continue.to.perform.the.functions.referred.to.the.“Quiescent”.and.“Alarm”.statuses..
“System Fault” (SyS LEd illuminated)
This.operating.condition.signals.that.the.system.is.blocked.as.the.result.of.a.temporary.or.permanent.malfunctioning.of.the.CPU,.detected.by.the.
watchdog..It.is.accompanied.by.an.acoustic.signal.(buzzer).indicating.the.failure..During.a.System.Fault,.the.functions.relating.to.the.“Quiescent”.
and.“Alarm”.conditions.are.not.operational.
“disablement condition” (dIS LEd illuminated)
This.operating.condition.signals.that.the.Alarm.signals.for.at.least.one.output.zone.have.been.set.to.a.Disablement.condition..The.system.can.
in.any.case.carry.on.the.functions.pertaining.to.the.“Quiescent”.condition.for.all.the.zones..and,.only.for.those.zones.that.are.not.disabled,.the.
functions.pertaining.to.the.“Voice.Alarm.Condition”..In.a.12-zone.system.with.two.interconnected.PA8506-V.units,.a.“Disabled.Status”.is.signalled.
on.both.units,.regardless.of.which.output.zone.is.affected.
“Automatic Emergency” (CONTrOL INPUT STATUS display with zones active)
This.indicates.a.sequence.of.operations.performed.from.an.external.peripheral.unit.connected.to.the.Control.Inputs..Depending.on.how.these.
inputs.are.programmed,.the.“Voice.Alarm.Condition”.or.an.Alarm.Reset.are.activated.
“Manual Emergency” (LEd of the EMErGENCy button ON/flashing)
This.procedure.is.performed.by.an.authorised.operator.using.the.manual.controls,.to.activate.VES.sources.or.to.reset.the.Alarms.(Manual.Alarm.
Reset)..The.operations.carried.out.in.the.Manual.Emergency.mode.have.a.higher.priority.than.those.activated.by.an.Automatic.Emergency..A.
PA8506-V.unit.or.an.emergency.unit.on.which.the.EMERGENCY.LED.is.illuminated.is.enabled.for.use.for.activating.VES.sources.or.for.resetting.
the.alarms..A.PA8506-V.unit.or.an.emergency.unit.on.which.the.EMERGENCY.LED.is.flashing.indicates.that.a.Manual.Emergency.has.been.
activated.from.a.remote.station.
dual / single-channel operation
If.the.amplifiers.for.the.“Music”.and.“Voice”.channels.are.both.operational,.the.PA8506-V.system.enables.two.signals.to.be.played.out.in.different.
zones,.operating.in.a.dual.channel.mode,.as.follows:
-. In.the.“Quiescent.condition”:.BGM.source.selected.via.the.MUSIC.MENU.(out.at.0dB.=.70V.constant.voltage).and.PA.source.with.the.highest.
priority.(out=.100V.constant.voltage).
-. In.the.“Voice.Alarm.Condition”:.ALERT.message.(out=.100V.constant.voltage).and.EVAC.message.(out.=.100V.constant.voltage).
-. In.the.“Voice.Alarm.Condition”,.with.the.extension.amplifier.for.a.system.with.a.total.output.power.of.490W:.ALERT.message.(out=.70V.
constant.voltage).and.EVAC.message.(out=.100V.constant.voltage).
By.default,.the.signal.from.the.emergency.microphone.is.always.sent.to.a.single.channel,.and.without.any.other.simultaneous.messages.
If. an. amplifier. assigned. to. the. “Voice”. channel. fails,. the. PA8506-V. automatically. switches. the. “Music”. amplifier. to. replace. it,. and. activates.
operation.in.the.single-channel.mode,.thus.enabling.one.signal.at.a.time.to.be.sent.out,.as.follows:
-. In.the.“Quiescent.condition”:.only.the.active.PA.source.with.the.highest.priority.(out=.100V.constant.voltage)..The.“Music”.channel.will.not.
be.available.and.the.wording.“NOT.AVAILABLE”.will.appear.on.the.Music.menu.display.
-. In.the.“Voice.Alarm.Condition”:.only.one.VES.source.at.a.time,.either.an.ALERT.or.EVAC.message.or.the.Emergency.microphone.(out=.100V.
constant.voltage)..The.second.emergency.channel.will.not.be.available.and.the.wording.“only.one.channel.available.-.FAULT.CONDITION”.
will.appear.on.the.display.
For.further.information.consult.Section.9,
“Fault warning condition”
.