36
PA8506-V
|
VES Compact System
PA8500-VES | Voice Evacuation System
System Manual | 2014
UK
8.5.1.4a EMErGENCy UNIT FAULT
..
diagnosing faults of the emergency units
From.the.VOICE.ALARM.FAULT.panel.(point.8.5.1.4),.press.numerical.key.4.
and.access.the.panel.displaying.the.diagnosis.of.the.emergency.units.
The.panel.is.split.up.into.two.sections..The.first.section.is.used.to.select.the.
address.of.the.station.and.the.second.to.display.the.faulted.items..
Use.the.+/-.knob.to.select.the.address.of.the.station.and.check.on.the.panel.
whether.there.are.any.faulted.items,.following.the.indications.in.the.figure.
provided.below.
Key
A
. field.for.selecting.an.address...
B
. field.showing.faults.
C
. address.with.flashing.dark.background:.station.with.cleared.failure.(resumed).
d
. address.with.white.background:.fault-free.station.
E
. address.with.dark.background:.station.with.at.least.one.on-going.fault.
F
. underscored.address:.cursor.for.selecting.an.address.
G
. label.with.dark.background:.faulty.item.
H
. label.with.white.background:.no.faults.detected.
Typology
Fault
Operation required
MIC.
Fault.detected.in.the.microphone.capsule.
Check.whether.the.microphone.and.stem.are.fitted.correctly.into.the.
connector. on. the. microphone. base;. try. making. an. announcement.
in.order.to.test.operation..If.the.fault.persists,.contact.your.Service.
Centre.
AUDIO
Fault. detected. on. the. audio. communication. line.
from.the.microphone.station.to.the.PA8506-V.unit.
Inspect.the.cable.connecting.the.station..Make.a.test.announcement.
in. order. to. check. operation.. If. the. problem. persists,. even. with.
the. announcement. played. out. correctly,. adjust. the. level. of. the. 20.
kHz. test. tone. following. the. procedure. indicated. under. point. 8.6.4.
“EMERGENCY.UNIT.CONFIG”.
DATA
Fault.detected.on.the.data.communication.line.from.
the.microphone.station.to.the.PA8506-V.unit.
Inspect. the. cable. connecting. the. station;. if. the. problem. persists,.
contact.your.Service.Centre.
EXP.
Fault.detected.in.the.station.selection.keypad.on.
the.12-zone.PMB132/12-V.unit.
If.the.fault.persists,.contact.your.Service.Centre.
PTT,.EME,.
EVAC
K01÷K12
Fault. detected. in. the. activation. key. on. the.
microphone.base.
The.associations.of.the.keys.are.shown.in.the.following.figure..
Check.the.functioning.of.the.key..If.the.problem.persists,.contact.
your.Service.Centre.
Tab..8.5.1.4c