34
PA8506-V
|
VES Compact System
PA8500-VES | Voice Evacuation System
System Manual | 2014
UK
8.5.1.3 LOUdSPK. LINE FAULT
diagnostics of line speaker units
From.the.FAULTS.panel.(point.8.5.1),.press.numerical.key.1.and.access.the.
panel.for.viewing.the.loudspeaker.line.diagnostics:.the.diagnostics.for.each.
output.zone.are.shown.as.indicated.in.the.following.table.
.
Press.ESC.to.return.to.the.FAULTS.panel.
Label Part being
diagnosed
Signalling
Cause
Action required
A
LL
OK
No.failure
-
Zone.1 Loudspeaker.lines
Zone.1
Short.A
Short.circuit.on.the.line.connected.to.
output.A.
Eliminate.the.short.circuit.and.
carry.out.a.MANUAL.RESET.of.
the.FAILURE.signal.(from.the.
OPERATOR.menu)
Zone.2 Loudspeaker.lines
Zone.2
Short.B
Short.circuit.on.the.line.connected.to.
output.B.
Zone.3 Loudspeaker.lines
Zone.3
Short.A+B
Short.circuit.on.both.lines.of.the.zone..
(Note.1)
Zone.4
Loudspeaker.lines
Zone.4
Impedance.Hi
Impedance.level.higher.than.acquired.
value.detected,.beyond.the.tolerance.set.
during.configuration.(Note.2)
Check.the.connections.of.the.speaker.
units.and.if.necessary.repeat.the.line.
acquisition. procedure. (ACQUIRE.
IMPEDANCE)
Zone.5
Loudspeaker.lines
Zone.5
Impedance.Low Impedance.level.lower.than.acquired.value.
detected,.beyond.the.tolerance.set.during.
configuration.(Note.2)
Zone.6 Loudspeaker.lines
Zone.6
Res..imp..Hi
Failure.(“Impedance.Hi”.signal).cleared
Access. the. Report. >. FAULTS. panel.
from.the.OPERATOR.menu.and.carry.
out.a.MANUAL.RESET.of.the.FAILURE.
signal
Res..imp..Low
Failure.(“Impedance.Low”.signal).cleared
Tab..8.5.1.3
Note 1:
It.may.happen.that.an.occasional.short.circuit.of.a.single.line.does.not.give.the.diagnostic.system.sufficient.time.to.identify.the.line.that.has.failed..
In.this.case,.the.message.“Short.A+B”.may.be.displayed.
Note 2:
.“Impedance.Hi”.and.“Impedance.Low”.failures.are.not.reported.if.the.tolerance.is.set.at.a.higher.level.than.the.measured.variation.of.the.
impedance.or.if.the.test.is.disabled..For.details.concerning.programming,.see.the.
SET TOLErANCE
.panel.(point.8.7.2).
8.5.1.4 VOICE ALArMS FAULT
diagnosing faults of the VES emergency sources
From. the. FAULT. panel. (point. 8.5.1),. press. numerical. key. 2. and. access.
the.panel.for.viewing.the.diagnostics.of.the.VES.emergency.sources..The.
diagnostic.state.of.each.item.monitored.is.reported,.as.shown.in.the.following.
table.
For.some.items.of.equipment.it.may.be.necessary.to.access.the.sub-panel,.
by.pressing.the.corresponding.numbered.key.
Press.ESC.to.return.to.the.panel.FAULTS.
Содержание PA8506-V
Страница 2: ......
Страница 4: ... PA8506 V VES Compact System PA8500 VES Voice Evacuation System System Manual 2014 UK ...
Страница 66: ......
Страница 67: ......