8.7 < CONFIGUrATION > MENU
Panel. for. selecting. options. pertaining. to. personnel. specifically.
trained. and. authorised. to. use. the. advanced. system. functions.
and. to. modify. the. configuration. parameters. for. starting. and.
maintaining.the.system..
A.password.for.accessing.these.functions.may.be.added.
The.options.of.the.
CONFIGUrATION
.Menu.enable.the.following.management.panels.to.be.accessed:
8.7.1
IMP. ACQUISITION
.panel.(via.the.
acquire > IMPEdANCE
option)
For.acquiring.and.storing.the.impedance.values.of.the.speaker.unit.lines,.which.is.necessary.for.system.initialisation.and.diagnostics.
8.7.2
SET TOLErANCE
.panel.(via.the.
set > IMP. TOLErANCE
option)
For.setting.the.tolerance.applicable.to.the.line.impedance..When.the.diagnostic.system.detects.impedance.that.is.out.of.tolerance,.a.“Fault.
Warning.Condition”.is.activated.
8.7.3
MESSAGES
.panel.(via.the.
set > MESSAGES
option)
Panel.for.transferring.the.audio.files.for.the.Alert.and.Evacuation.messages.from.an.external.Flash.Memory.Stick.to.the.resident.memory.of.the.
PA8506-V,.for.future.use.in.“Voice.Alarm”.emergency.conditions.
8.7.4
ALArM LEVEL
panel.(via.the.
set > ALArM LEVEL
option)
Panel.for.adjusting.the.output.volume.of.the.VES.sources:.Emergency.Microphones.and.Alarm.Messages.
8.7.5
AMPLIFIEr MOdE
panel.(via.the.
set > AMPLIFIEr MOdE
option)
For.setting.the.system.operating.mode.in.relation.to.the.presence.or.otherwise.of.an.external.amplifier.
8.7.6
IP AddrESS
panel.(via.the.
IP address
option)
For.setting.the.networking.parameters.for.accessing.the.system.functions.via.a.Web.Server.
8.7.7
PASSWOrd
panel.(via.the.
Password
option)
Panel.for.enabling,.disabling.and.customising.the.password.for.accessing.the.system.service.levels.
< SErVICE >
Connection.to.the.SERVICE.menu.for.technical.personnel.having.the.necessary.password..It.is.used.to.change.the.operating.parameters.of.the.
PA8506-V.system,.up-dating.the.firmware.and.servicing.it.
Note:
The settings of the Service Menu are not covered in this Manual.
If.an.access.password.has.been.enabled,.at.the.time.of.configuration.the.
CONFIGUrATION ACCESS
.panel.will.be.displayed:
-.enter.the.four-digit.password.then.press.OK.to.proceed,.
or
-.press.ESC.to.return.to.the.MAIN.page.
The.default.password.is.3333.
.
Once.the.CONFIGURATION.Menu.is.accessed,.all.the.options.illustrated.
earlier.in.the.“AUDIO.SETTING”,.“INSPECTION”.and.“CONFIGURATION”.
menus.will.be.shown,.as.well.as.the.following.new.options.specific.to.the.
CONFIGURATION.menu.
Turn.the.knob.to.browse.through.the.options.listed:
•.
acquire > IMPEdANCE
•.
set > IMP. TOLLErANCE
•.->-
•.->-
•.
set > MESSAGES
•.
set > ALArM LEVEL
•.->-
•.
set > AMPLIFIEr MOdE
•.->-
•.->-
•.
IP address
•.
Password
<.
SErVICE
.>
•.
Exit > Logout
Press.OK.to.select.the.required.item,.or
-.press.ESC.to.return.to.the.MUSIC.panel.
-.press.MENU.to.return.to.the.MAIN.page..
The.characteristics.of.the.specific.panels.of.the.
CONFIGUrATION
.Menu.are.illustrated.below..For.the.other.available.options,.refer.to.the.
appropriate.sections.above..
At.the.end.of.the.setup,.log.out.by.selecting.“
Exit> Logout
”.as.described.in.paragraph.8.6.8.