57
System Manual | 2014
PA8500-VES | Voice Evacuation System
UK
PA8506-V
|
VES Compact System
If.necessary,.repeat.point.
3
).to.diversify.the.messages.to.the.various.different.zones..
The.EVAC.message.has.priority.over.the.ALERT.message..
The.Emergency.Microphone.has.priority.over.both.pre-recorded.messages.
Access.the.external.peripheral.unit.
connected.to.the.CONTROL.INPUT.
contacts.
De-activate.all.the.contacts.applied.to.
the.CONTROL.INPUTS.
The.system.will.continue.to.broadcast.any.manually.
activated.messages..
4) End of the Automatic Emergency function, if any, from the input contacts
Exit.from.Manual.Emergency
Press.the.
Emergency
.key.once
The.system.will.return.to.the.MUSIC.panel.
End of the Manual Emergency and return to a Quiescent Condition
8.9.3 Access to the system for handling a Manual Emergency
•. Press.the.red.EMERGENCY.key..The.display.will.show.the.current.
status. of. each. zone. and. a. message. indicating. the. procedure. for.
accessing.the.Emergency.mode.or.the.Operator.mode.
•. Press.the.red.EMERGENCY.key.again.within.about.15.seconds.from.
the. first. time. (or. exit. by. pressing. ESC. to. return. to. the. Main. page.
menu)...
.
The.EMERGENCY.will.light.up.steadily.to.indicate.that.a.condition.of.
Manual.Emergency.has.been.activated.
• Operation during manual management of an emergency
Following.access,.the.display.will.show.the.status.of.the.zones,.indicating.–.if.appropriate.-.the.messages.currently.activated.automatically.via.the.
“Control.Inputs”..By.default,.when.first.accessed,.all.the.zones.have.already.been.selected.for.a.general.emergency..Any.disabled.zones.will.not.
be.available.(see.the.DISABLEMENT.section).
When.a.current.Manual.Emergency.is.in.progress,.if.no.General.Reset.of.the.alarms.is.carried.out,.any.new.activations.of.input.contacts.will.
be.carried.out.for.the.free.zones.on.the.basis.of.how.the.activated.contact.has.been.programmed.(see.section.8.6.1.Set>.CONTROL.INPUTS)..
Following.a.GENERAL.RESET.of.the.alarms,.any.re-activation.of.the.input.contacts.will.have.no.effect.on.the.zone.outputs.
When.the.system.is.working.correctly.with.the.double.channels,.the.display.will.show:
“PTT,.EVAC.or.ALERT.for.general.call,.ESC.muting.beep”.
In.the.event.of.failure.of.an.amplifier,.on.the.other.hand,.the.text.on.the.display.will.read:
“Only.one.channel.available.FAULT.CONDITION”
to.show.that.only.one.channel.is.operational.
In.any.case,.manual.resetting.of.the.beep.signalling.a.failure.is.always.available,.by.pressing.directly.the.ESC.key...For.further.information.
concerning.resetting.of.the.beep.see.point.8.5.1.1.
While.an.Emergency.message.is.being.broadcast,.it.is.possible,.if.required,.to.change.the.selection.of.zones,.as.indicated.under.2,.to.diversify.
broadcasting.of.the.Emergency.message,.sending.two.separate.messages.to.two.different.groups.of.zones.(operation.with.double.channel).
Any.current.messages.that.have.already.been.activated.automatically.via.an.external.peripheral.unit.have.a.lower.priority.than.the.message.
activated.manually,.and.it.is.therefore.possible.to.change.the.message.being.broadcast.by.activating.the.manual.function.