35
System Manual | 2014
PA8500-VES | Voice Evacuation System
UK
PA8506-V
|
VES Compact System
Label
Part being diagnosed
display
Cause
Action required
Tutti
Tutti
OK
No.failure
-
N.T.
Diagnostics.disabled.during.
configuration.(see.Set>.
BACKGROUND.TEST.menu).
-
Res.
Failure.(Fault.signal).cleared
Access.the.Report>.FAULTS.panel.from.the.
OPERATOR.menu.and.carry.out.a.MANUAL.
RESET.of.the.FAILURE.signal.
Fire.Microphone Hand-held.emergency.
microphone
Fault
Current.failure.due.to
critical path
Check.the.connection.and.operation.of.the.
hand-held.emergency.microphone.
Check.the.volume.setting.from.the.Set>.ALARM.
LEVEL.panel.in.the.CONFIGURATION.menu.
(recommended:.0.to.16).
If.the.failure.persists,.contact.Servicing.
2-Evac.Message Recorder/player.of.the.
emergency.EVAC.message
Fault
Presence.of.two.or.more.failures.
(see
Tab. 8.5.1.4b)
Press.key.2.to.access.the.dedicated.“EVAC.
MESSAGE.FAULT”.sub-panel...See.the.type.of.
fault.in.Table.8.5.1.4b.
3-Alert.Message Recorder/player.of.the.
emergency.ALERT.message
Fault
Presence.of.two.or.more.failures.
(see
Tab. 8.5.1.4b)
Press.key.3.to.access.the.dedicated.“ALERT.
MESSAGE.FAULT”.sub-panel..See.the.type.of.
fault.in.Table.8.5.1.4b.
4-Emergency.
Unit
Emergency.microphone.
stations.
Fault
At.least.one.microphone..
station.faulty..
Press.key.4.to.access.the.dedicated.
“EMERGENCY.UNIT.FAULT”.sub-panel.under.
point.8.5.1.4a
Res.
Fault.cleared.with.reference.to.a.
fault.signalled.earlier.
Press.key.4.to.access.the.dedicated.
“EMERGENCY.UNIT.FAULT”.sub-panel.
and.check.the.address.of.the.faulty.station..
Access.the.“report>.FAULTS”.panel.from.the.
OPERATOR.Menu.and.RESET.the.FAULT.
signal.manually.
Emerg..Button
Key.for.accessing..
MANUAL.EMERGENCY
Fault
Communication.error
Check.operation.of.the.key..If.the.failure.
persists,.contact.Servicing.
6-Remote.Link
Intercommunication.with.
remote.PA8506-V
Fault
If.the.problem.was.caused.by.the.change.from.
a.12-zone.system,.to.a.6-zone.system,.carry.
out.the.“Restore.the.6-zone.configuration”.
procedure.as.indicated.under.point.8.6.6.2.
As.an.alternative,.press.key.6.to.access.the.
dedicated.“REMOTE.LINK.FAULT”.sub-panel..
Check.the.connecting.cable.between.the.two.
PA8506-V.units.for.the.REMOTE.LINK...
If.the.failure.persists,.contact.Servicing.
Label
Part being diagnosed
Cause
Action required
Memory.checksum.error
Memory.checksum
On-going.fault.due.to.internal.error
Try.re-writing.the.message.(see.the.
MESSAGES.panel.in.the.CONFIGURATION.
Menu)..If.the.fault.persists,.contact.your.Service.
Centre.
Open.file.error
File.diagnostics
On-going.fault.due.to.file.
not.found
Frame.I2S.error
Audio.communication
On-going.fault.due.to.internal.error
If.the.fault.persists,.contact.your.Service.Centre.
Data.I2S.error
Data.communication
On-going.fault.due.to.internal.error
Memory.checksum.resumed
Open.file.resumed
Frame.I2S.resumed
Data.I2S.resumed
See.faulted.items
Fault.cleared.following.earlier.
signalling.of.
fault
.
Access.the.report>.FAULTS.panel.from.the.
OPERATOR.Menu.and.RESET.the.FAULT.
signal.manually.
Types.of.fault.affecting.the.Emergency.Message.recorder/player,.shown.in.the.“EVAC.MESSAGE.FAULT”.or.“ALERT.MESSAGE.FAULT”.sub-
panels.
Tab..8.5.1.4a
Tab..8.5.1.4b