25
System Manual | 2014
PA8500-VES | Voice Evacuation System
UK
PA8506-V
|
VES Compact System
8.2 INITIALISING THE SySTEM
•.
Password
From.the.MAIN.page,.select.the.CONFIGURATION.menu.and.press.OK.to.confirm.your.choice..If.the.restriction.calling.for.access.with.a.password.
has.been.enabled,.the.“CONFIGURATION.ACCESS”.screen.will.appear:.enter.the.4-digit.code.of.the.password,.then.press.OK.to.confirm.(the.
default.password.is.3333,.see.point.8.7).
•.
resetting the BEEP
Failure.signals.may.occur.during.the.initialisation.procedure.due.to.the.differences.between.the.configuration.of.the.system.as.connected.and.the.
default.settings..To.reset.the.acoustic.signal.(beep),.access.the.“Report>.FAULT”.menu.and.press.the.RESET.key..For.details.consult.“FAULT”.
(see.point.8.5.1.1).
.
o.
Path
:.HOME./.CONFIGURATION./.
report>.FAULT.(press.the.RESET.key)
•.
External amplifier
Configure.the.PA8506-V.with.or.without.an.external.amplifier..For.details.see.“AMPLIFIER.MODE”.(see.point.8.7.5).
.
o.
Path
:.HOME./.CONFIGURATION./.
set>.AMPLIFIER.MODE
•.
Acquisition of impedances
From.the.MUSIC.menu,.set.all.the.outputs.with.music.“OFF”..For.details,.see.“MUSIC.menu”.(see.point.8.3.4).
Acquire. the. new. loading. impedances. of. the. loudspeaker. lines,. as. indicated. under. “IMP..ACQUISITION”. and. enable. the. test. by. setting. the.
measurement.tolerances.
.
o.
Path
:.HOME./.CONFIGURATION./.
acquire>.IMPEDANCE./.IMP..ACQUISITION.(press.the.OK.key)
.
o.
Path
:.HOME./.CONFIGURATION./.
set>.TOLLERANCE./.SET.TOLLERANCE
•.
diagnostics for 24 VdC power supply
If. the. auxiliary. 24. VDC. power. supply. has. been. connected,. enable. the. diagnostic. test. by. setting. “24. VDC. . P.S.. ON”,. as. illustrated. under.
“BACKGROUND.TEST”.(see.point.8.6.3.3)...
.
o.
Path
:.HOME./.CONFIGURATION./.
set>.Background.test./.4-Power.supplies
•.
Emergency messages
Load.the.*.WAV.files.for.the.ALERT.and.EVAC.messages.in.the.resident.memory.of.the.PA8506-V,.as.illustrated.under.“MESSAGES”.(see.point.
8.7.3).
.
o.
Path
:.HOME./.CONFIGURATION./.
set>.Messages
•.
Input contacts
Based.on.the.provisions.of.the.Emergency.and.Evacuation.Plan.(EEP),.programme.the.input.contacts.connected.to.the.external.peripheral.unit.
suitably..For.details.see.under.“CONTROL.INPUTS”.(see.point.8.6.1).
.
o.
Path
:.HOME./.CONFIGURATION./.
set>.CONTROL.INPUTS
•.
Output contacts
Based.on.the.provisions,.if.any,.relating.to.the.specific.system,.programme.the.output.contacts.connected.to.the.external.peripheral.units.suitably..
For.details.see.under.“CONTROL.OUTPUTS”.(see.point.8.6.2).
.
o.
Path
:.HOME./.CONFIGURATION./.
set>.CONTROL.OUTPUT
•.
Volume control
Adjust.the.output.volume.of.the.VES.sources.suitably.so.as.to.ensure.that.the.messages.are.as.intelligible.as.possible..The.level.set.will.be.used.
for.”Voice.Alarm.Conditions”.and.will.be.the.same.for.all.the.zones..To.adjust.the.volume.of.the.Emergency.Microphone.and.of.the.ALERT.and.
EVAC.messages,.follow.the.instructions..provided.under.“ALARM.LEVEL”.(see.point.8.7.4).
.
o.
Path
:.HOME./.CONFIGURATION./.
set>.ALARM.LEVEL
•.
resetting failures
Upon.completion.of.the.system.configuration,.the.reports.concerning.failure.that.have.been.stored.and.cleared.should.be.cancelled.(RESOLVED)..
A.FAULT.RESET.should.therefore.be.carried.out.as.indicated.under.“FAULTS”.(see.point.8.6.5.1)..
.
o.
Percorso
:.HOME./.CONFIGURATION./.
report>.FAULT,.access.the.subpanels.for.viewing.failures.
.
•.
After initialising the system
After.completing.the.system.initialisation.procedure,.LOG.OUT.in.order.to.reinstate.any.access.restrictions.associated.with.passwords.(see.point.
8.6.7).
.
o.
Percorso
:.HOME./.CONFIGURATION./.
Exit>.Logout.(press.the.OK.key).