42
PA8506-V
|
VES Compact System
PA8500-VES | Voice Evacuation System
System Manual | 2014
UK
8.6.1
CONTrOL INPUTS
.
Local input contacts
This panel is for programming each of the eight local control input (CONTROL
INPUTS), for which it is possible to choose the type of activation contact, to
enable diagnostics for the connecting line, to associate a type of pre-recorded
emergency message with each output zone or to carry out a general reset of all
zones.
For details concerning the connection, see point 5.2.
CAUTION: Activation of the input contacts by an external peripheral unit
generates an Automatic Emergency. For details about management of Automatic
Emergencies, see point 8.8 “Automatic Emergency”.
8.6.1.1
.
Programming the input contacts
Note:.The.display.will.show.the.programming.that.has.been.set..
Choice of the input contact:
:
Turn.the.+/-.knob.to.select.the.contact.number:
.
>.INPUT:.
from 1 to 8
Choice of the type of activation of the contact, Normally Open (N.O.) or normally closed (N.C.):
Press.MENU.to.select.the.state.of.the.contact.for.activation:
.
>.“
Active if Close
”:.cconnect.the.activation.contact.as.N.O.
.
>.“
Active if Open
”:connect.the.activation.contact.as.N.C.
.
Setting the diagnostics for the line connecting the contact:
Press.OK.to.enable.or.disable.diagnostics:
.
>.
Surveillance NO
:.diagnostics.disabled.
.
>.
Surveillance yES
:.diagnostics.enabled
Note:.With.diagnostics.enabled,.the.balancing.resistors.must.be.installed.on.the.contact.of.the.activating.external.peripheral.unit.(see.point.5.2).
Configuration of the messages sent to the output zones:
Press.the.numerical.key.of.zones.1.to.6.cyclically.to.associate.the.zones.in.question.with.the.required.message:.
.
>.
NONE
:.No.associated.message
.
>.
EVAC
:.Pre-recorded.Evacuation.message
.
>.
ALErT
:.Pre-recorded.Alert.message
Configuring the contact for a GENErAL rESET of the alarms:
Press.the.RESET.key..The.label.indicating.the.state.of.each.zone.will.show.RESET.
.
On.completing.the.programming,.press.ESC.to.return.to.the.OPERATOR.Menu.
N.B.:
If more than one contact associating various different events in the same area is activated, the event with the highest priority level will be
selected, on the basis of the table provided on page 2 in Section 6.
8.6.1.2
.
Programming the input contacts in a 12-zone system
The.two.PA8506-V.units.are.considered.to.be.two.separate.systems..Follow.the.procedure.indicated.in.the.foregoing.paragraph.for.each.of.
the.two.units..