System Manual | 2014
UK
5.2 LOCAL INPUT CONTACTS
Examples.of.connection.of.control.inputs.with.programming.of.the.inputs.for.use.with:
Example A:
.activation.contacts.Normally.Open.WITHOUT.monitoring.of.connecting.line.
Example B:
.activation.contacts.Normally.Closed.WITHOUT.monitoring.of.connecting.line.
Example C:
.activation.contact.Normally.open.WITH.monitoring.of.connecting.line.
Example d:
activation.contact.Normally.closed.WITH.monitoring.of.connecting.line.
When.monitoring.a.connecting.line,.it.is.necessary.to.connect.the.balancing.resistors.in.the.proximity.of.the.activation.contact..For.details.about.
the.control.input.programming.modes,.refer.to.the.Section.on.“
set > CONTrOL INPUTS
”.(par..8.6.1).
N.C. contact
N.O. contact
N.C. contact
Example A
.
Set.the.following.parameters.for.INPUT.1:
•.“Active.if.Close”
•.“Surveillance.NO”
Example B
.
Set.the.following.parameters.for.INPUT.3:
•.“Active.if.Open”
•.“Surveillance.NO”
Example C
.
Set.the.following.parameters.for.INPUT.5:
•.“Active.if.Close”
•.“Surveillance.YES”
Example d
.
Set.the.following.parameters.for.INPUT.7:
•.“Active.if.Open”
•.“Surveillance.YES”
Monitored.lines
r
.=.10.k
W
.±.5%
External peripheral unit
N.O. contact
5.2.1 Local input contacts for a 12-zone system
The.two.PA8506-V.units,.connected.to.one.another.so.as.to.form.a.12-zone.system,.are.managed.as.two.separate.systems..The.contacts.for.
activating.the.external.peripheral.unit.have.to.be.connected.separately.to.each.PA8506-V.unit..Reference.should.be.made.to.the.heading.“set.>.
CONTROL.INPUTS”.(point.8.6.1).for.programming.each.contact.connected.for.each.of.the.PA8506-V.units.
C
A
B
d