8.5.1
FAULTS
For viewing the failed components
Six.groups.are.listed,.with.a.generic.indication.of.the.fault.condition.
From.this.panel.it.is.possible.to.reset.the.beep.(see.point.8.5.1.1).
The.categories.of.failed.parts.and.generic.signalling.of.their.states.are.shown.in.the.
table.below.
Press.the.associated.numerical.key.(1-6).to.select.the.sub-panel.and.view.the.details.
of.the.failure,.as.illustrated.under.points.8.5.1.3.to.8.5.1.8.below
or.
Press.ESC.to.return.to.the.INSPECTION.panel.
8.5.1.1 Manual resetting of the acoustic signal (beep) by acknowledging the failure
When.the.built-in.monitoring.system.of.the.PA8506-V.detects.a.new.fault,.the.acoustic.signal.(beep).is.automatically.activated.and.sounded.at.any.
and.all.emergency.units.and,.in.a.12-zone.system,.also.on.the.remote.PA8506-V.
To.reset.the.beep,.access.the.“FAULTS”.menu.showing.the.list.of.six.groups.of.diagnostic.signals,.of.which.at.least.one.will.show.a.FAULT.condition..
To.do.this,.follow.the.path:
HOME/INSPECTION/report>.FAULTS
.
•.
Press the rESET key
The.beep.will.be.reset.on.all.the.units.within.the.system.and.on.any.remote.emergency.units..The.FAULT.LED.will.remain.active.to.indicate.that.
a.“Fault.Condition”.continues.to.exist..If.the.Fault.LED.is.steady.ON,.it.will.be.possible.to.identify.the.faulty.item.of.equipment.by.accessing.the.
options.of.the.FAULT.menu.(see.points.8.5.1.3.to.8.5.1.8).to.find.the.fault..If.the.Fault.LED.is.flashing,.this.means.that.the.fault.has.to.do.with.the.
remote.PA8506-V.unit,.in.which.case.you.should.access.the.FAULTS.menu.proceeding.via.the.other.PA8506-V.unit.
After.resetting.the.beep,.it.will.be.possible.to.return.to.the.MUSIC.panel.by.pressing.repeatedly.the.ESC.key.
8.5.1.2 Automatic resetting of the acoustic signal (beep) following clearing of a failure
If.the.cause.of.a.failure.is.cleared.before.the.beep.is.reset.manually,.the.PA8506-V.will.reset.the.beep.automatically,.extinguish.the.FAULT.LED.
and.indicate.RES.(RESOLVED).in.the.label.of.the.part.that.had.FAILED..The.RESOLVED.signal.will.be.stored.until.a.MANUAL.RESET.of.the.
failure.signal.is.carried.out.from.the.FAULTS.panel.via.the.OPERATOR.menu.
Label
diagnostic category
See panel
Signalling Cause
1-Loudspk.Line
Loudspeaker.lines
LOUDSPK..LINE.FAULT
ALL
OK
No.faults
2-Voice.Alarms
VES.emergency.sources
VOICE.ALARMS.FAULT
3-Amplifiers
Power.amplifiers.
Ground.fault.loudspeaker.lines
AMPLIFIER.FAULTS
4-Power.Supply
Primary.and.secondary.power.supplies.
Management.memory.display
POWER.SUPPLY.FAULTS
FAULT
At.least.1.fault.detected..
and.on-going.
5-Control.Input
Local.input.contacts
CONTROL.INPUT.FAULT
RES
At.least.1.fault.cleared..
and.no.on-going.faults
6-Communication PA8506-V.internal.data.
communication
COMMUNICATION.FAULT
Tab. 8.5.1.1