40
PA8506-V
|
VES Compact System
PA8500-VES | Voice Evacuation System
System Manual | 2014
UK
8.5.2
IMP. rEAL TIME
.
real-time line impedance
Panel.for.checking.the.impedance.values.measured.in.real.time,.and.percentage.
variations. from. the. value. stored. during. start-up,. using. the. “Line. impedance.
acquisition”.procedure..The.6.zones.are.listed,.with.their.impedances,.measured.in.
Ohms..The.measure.indicated.is.referred.to.both.lines.-.A.and.B.-.connected.to.the.
zone.output..If.the.percentage.of.variation.exceeds.the.level.of.tolerance.set.at.the.
time.of.configuring.the.system,.a.“LOUDSPK.LINE.FAULT”.due.to.an.excessively.
high.or.low.impedance.(Impedance.Hi.or.Impedance.Low).will.be.signalled.
Press.ESC.to.return.to.the.INSPECTION.panel.
8.5.3
CHECK MESSAGES
.
diagnosis of stored messages
Panel.for.checking.all.stored.data.for.each.of.the.emergency.messages..Referring.to.
the.two.messages.EVAC.and.ALERT,.it.shows.the.checksum.data.in.alphanumeric.
format.(see.example.in.the.figure)..A.different.checksum.data.is.generated.when.the.
new.message.is.stored.
Press.ESC.to.return.to.the.INSPECTION.panel.
Note:
if several input contacts are activated simultaneously, with
different programming of the messages in relation to the zones, for
each zone output the system will enable the event with the highest
priority (see table). The CONTROL INPUT STATUS panel will
therefore show the zone outputs as configured following enabling of
all the active contacts.
Maximum.priority
General.reset.of.messages.(RESET)
High.priority
Pre-recorded.Evacuation.message.(EVAC)
Low.priority
Pre-recorded.Alert.message.(ALERT)
Minimum.priority
No.event.(NONE)
8.5.4
CONTrOL INPUTS STATUS
.
Status of the local input contacts
Panel.for.viewing.the.status.of.the.local.input.contacts.(CONTROL.INPUTS)..A.list.of.
the.input.contacts.activated.by.external.peripheral.units.is.provided..The.CONTROL.
INPUT. STATUS.panel. shows. the. active. inputs,. both. if. no. events. are. associated.
with.them.and.if.an.output.message.event.is.associated.with.them..In.the.event.of.
activation. of. a. programmed. CONTROL. INPUT,. the. PA8506-V. system. will. trigger.
an.“Alarm.Condition”.(VOICE.ALARM),.cause.the.ALARM.LED.to.light.up.and.the.
CONTROL. INPUT. STATUS. panel. to. be. displayed. automatically..The. display. will.
show. a. list. of. all. the. active. inputs. (whether. programmed. or. otherwise). and. will.
indicate.the.type.of.pre-recorded.message.being.output.to.each.zone..In.the.event.
of.an.active.input.contact.programmed.for.a.GENERAL.RESET,.the.ALARM.LED.
will.be.extinguished.
For.further.information.concerning.programming,.consult.point.8.6.1,.OPERATOR/Set>.CONTROL.INPUTS...For.details.on.activity.in.
the.“Voice.Alarm.Condition”,.consult.point.8.8.Automatic.Emergency.–.Voice.Alarm.Condition.
Press.ESC.to.return.to.the.panel.INSPECTION.
8.5.5
INdICATOrS TEST
.
Check of the functionality of the visual and audio signal elements
Panel. for. checking. speaker. functionality. (BEEP),. display. and. operating. emergency. LED. indicators..All. LEDs. on. the. front. panel. (excluding.
‘ON’.LED).and.the.EMERGENCY.key.LED.are.flashing..Horizontal.bar.scrolls.on.the.display.and.beep.warning.tone.are.ON...The.functionality.
of.the.built-in.speaker,.all.LEDs.and.all.the.display.pixels.are.checked..Please.contact.Support.in.case.of.failure..Press.ESC.to.return.to.the.
INSPECTION.panel.