ZONE LISTS
Programming the groups of zones activated by a voice source
Panel.for.setting.the.groups.of.the.zones.selected.during.the.announcement.from.
a.“voice”.source.that.activates.the.Precedence.or.VOX.functions..It.is.possible.to.
create.up.to.36.lists.that.occupy.the.six.zones.of.the.PA8506-V.unit.to.which.the.
voice.source.is.connected:
•..
Programming a zone list:
>. Use.the.+/-.knob.to.select.the.number.of.the.list.you.wish.to.programme.(ZONE.
LISTS.from.1.to.36)..Refer.only.to.the.“PA8506-V.ADDRESS:.1”.unit..
>. Activate. or. de-activate. announcing. in. the. zone. concerned. by. pressing. and.
releasing.the.corresponding.numbered.key:
. OFF.=.zone.excluded
. ON.=.zone.active
8.4.7
dO NOT dISTUrB
disabling music and service announcements
Panel.for.setting.the.Do-Not-Disturb.function.for.each.output.zone.
This.function.is.operational.only.when.the.system.is.in.the.Quiescent.condition..It.
can.be.used.to.enable.protection.of.the.output.zones.to.stop.music.and.service.
announcements.being.sent.to.it.from.the.PA.sources..
The.criterion.for.activation.of.this.prevention.is.associated.with.the.priority.of.the.PA.
Source.involved..When.a.zone.is.in.the.“Do.Not.Disturb”.mode,.the.display.referred.
to.the.MUSIC.panel.will.show.the.
dNd
.label.on.the.status.bar.for.that.zone.
•..
Setting the dNd function for each zone:
Hold.the.numerical.key.(1-6).associated.with.the.zone.to.be.programmed.down.and.turn.the.+/-.knob.to.select.one.of.the.following.
modes:
•.V+M:.Do.Not.Disturb.function.disabled..The.zone.will.broadcast.music.and.announcements.from.all.the.PA.sources.
•.V>0:. The.zone.will.broadcast.only.the.announcements.from.all.the.PA.sources..Music.will.not.be.broadcast.
•.V>1:. The.zone.will.broadcast.only.announcements.from.the.PA.sources.with.priority.levels.from.2.to.7..Music.will.not.be.broadcast.
•.V>2:. The.zone.will.broadcast.only.the.announcements.from.the.PA.sources.with.priority.levels.from.3.to.7..Music.will.not.be.broadcast.
•.V>3:. The.zone.will.broadcast.only.the.announcements.from.the.PA.sources.with.priority.levels.from.4.to.7..Music.will.not.be.broadcast.
•.V>4:. The.zone.will.broadcast.only.the.announcements.from.the.PA.sources.with.priority.levels.from.5.to.7..Music.will.not.be.broadcast.
•.V>5:. The.zone.will.broadcast.only.the.announcements.from.the.PA.sources.with.priority.levels.from.6.to.7..Music.will.not.be.broadcast.
•.V>6:. The.zone.will.broadcast.only.the.announcements.from.the.PA.sources.with.priority.level.7..Music.will.not.be.broadcast.
•.OFF:. The.zone.is.blocked.for.announcements.from.all.PA.sources.up.to.priority.level.7.and.for.music..
.
Only.emergency.messages.and.announcements.broadcast.by.PMB132-V.and.PMB132/12-V.emergency.units.can.be.broadcast.
Press.ESC.to.return.to.the.AUDIO.SETTING.menu.
The.RESET,.ALERT,.EVAC,.OK.and.MENU.keys.are.not.operational.
Note
:.The.DND.function.is.not.affected.by.the.programming.of.the.paging.zones.associated.with.the.PA.source.and.has.priority.over.it..No.
feedback.is.sent.to.the.PA.Source.to.indicate.that.the.zone.is.engaged..Thus,.for.example,.a.microphone.programmed.for.announcements.to.all.
zones.will.broadcast.the.call.only.to.those.zones.that.are.enabled,.while.those.for.which.the.DND.function.is.active.will.remain.mute.
Note:
.The.current.firmware.version.enables.programming.only.for.the.six.zones.of.the.local.PA8506-V.unit..In.a.12-zone.system,.with.two.
PA8506-V.units.connected.to.one.another,.it.is.not.possible.to.relay.the.voice.source.activated.via.Precedence.or.VOX.to.the.remote.unit..Thus,.
the.Zone.Lists.referred.to.the.“PA8506-V.ADDRESS:.2”.unit.cannot.be.programmed.
Press.ESC.to.return.to.the.menu.AUDIO.SETTING..
The.RESET,.ALERT,.EVAC.and.MENU.keys.are.not.operational.