13
Chapter 1
System Outline
●
The main line is the longest route distributed from the controller.
●
The branch lines are the routes branched from the main line.
NOTE
The total cable length should satisfy the conditions shown in the following table:
Transmission mode
Total cable length (m)
A
100
B
400
C
1,600
The maximum transmission distance (between D and G) will be as follows:
●
A mode: 50m
The maximum length is 50m regardless of the cable conductor cross section (0.3 to 2.0mm
2
) and the number
of nodes (1 to 256 nodes).
●
B mode
Conductor
cross
section
(mm
2
)
Number of nodes and maximum transmission length (m)
Up to 224 nodes
Up to 256
nodes
0.3
180
0.5
200 (full specification for B mode)
0.75
1.25
2.0
●
C mode
Conductor
cross
section
(mm
2
)
Number of nodes and maximum transmission length (m)
Up to 32
nodes
Up to 64
nodes
Up to 96
nodes
Up to 128
nodes
Up to 160
nodes
Up to 192
nodes
Up to 224
nodes
Up to256
nodes
0.3
570
440
350
300
260
220
200
180
0.5
710
580
490
420
370
330
300
0.75
780
670
590
530
480
1.25
800 (full specification for C mode)
2.0
●
Voltage drop b24V and 0V is not considered. For this reason, calculate this volt-
age drop value, and use a local power supply unit, etc. For a detailed description, refer to
the ‘
S-LINK V User’s Manual
.’
● The conductor cross section of the exclusive 4-core flat cable (
SL-RCM
□) is 0.5mm
2
.
●
Wire the
S-LINK V
system while observing the transmission distance specifications de
-
scribed above. In addition, use the cables that satisfy the specifications described above.
●
To select applicable cables, refer to the ‘
S-LINK V User’s Manual
.’
NOTE
Содержание SL-VGU1-C
Страница 2: ...2 ...
Страница 5: ...5 Before Using This System ...
Страница 11: ...11 Chapter 1 Designing System ...
Страница 20: ...20 Chapter 1 MEMO ...
Страница 21: ...21 Chapter 2 SL VGU1 C Gateway Controller for CC Link ...
Страница 64: ...64 Chapter 2 MEMO ...
Страница 65: ...65 Chapter 3 SL VGU1 D Gateway Controller for Devicenet ...
Страница 94: ...94 Chapter 3 MEMO ...