88
Chapter 3
Starting
System setting
After turning on the power of the
S-LINK V
system for the first time, be sure to carry out system setting.
After system setting, the system can recognize the addresses of the connected
S-LINK V
units, and the rec-
ognized addresses will be stored in the EEPROM. After this, errors 3, 4 and 5 will be detected using the recog-
nized address data stored in the EEPROM.
Since the address data of the connected units is stored in the EEPROM, it is not necessary to carry out system
setting each time after turning on the power. For a detailed description of system setting method, refer to page
80 ‘
CONFIG Mode
.’
If error 3 or 4 appears on the address display, the system has one of the following problems. Solve
the problem, and then be sure to carry out system setting. If system setting is carried out without
solving the problem, system setting may not be carried out properly.
●
The line is disconnected between the I/O units of the system.
●
An I/O unit is added after system setting.
CAUTION
Presetting
In the
SL-VGU1-D
, 16 I/O patterns are preliminarily stored as the initial values.
To change the set I/O pattern, switch the transmission mode to the CONFIG mode first, and then select a de
-
sired presetting pattern number (0 to F).
The presetting pattern numbers stored as the initial values are shown in the following table:
Address
Presetting pattern number
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0 to 31
No presetting
IN
IN
IN
IN
IN
IN
IN
IN
OUT OUT OUT OUT OUT OUT OUT
32 to 63
IN
IN
IN
IN
IN
IN
IN
IN
OUT OUT OUT OUT OUT OUT OUT
64 to 95
IN
IN
IN
IN
IN
IN
IN
OUT OUT OUT OUT OUT OUT OUT OUT
96 to 127
IN
IN
IN
IN
IN
IN
IN
OUT OUT OUT OUT OUT OUT OUT OUT
128 to 159
IN
IN
IN
IN
IN
IN
OUT OUT OUT OUT OUT OUT OUT OUT
IN
160 to 191
IN
IN
IN
IN
IN
IN
OUT OUT OUT OUT OUT OUT OUT OUT
IN
192 to 223
IN
IN
IN
IN
IN
OUT OUT OUT OUT OUT OUT OUT OUT
IN
IN
224 to 255
IN
IN
IN
IN
IN
OUT OUT OUT OUT OUT OUT OUT OUT
IN
IN
256 to 287
IN
IN
IN
IN
OUT OUT OUT OUT OUT OUT OUT OUT
IN
IN
IN
288 to 319
IN
IN
IN
IN
OUT OUT OUT OUT OUT OUT OUT OUT
IN
IN
IN
320 to 351
IN
IN
IN
OUT OUT OUT OUT OUT OUT OUT OUT
IN
IN
IN
IN
352 to 383
IN
IN
IN
OUT OUT OUT OUT OUT OUT OUT OUT
IN
IN
IN
IN
384 to 415
IN
IN
OUT OUT OUT OUT OUT OUT OUT OUT
IN
IN
IN
IN
IN
416 to 447
IN
IN
OUT OUT OUT OUT OUT OUT OUT OUT
IN
IN
IN
IN
IN
448 to 479
IN
OUT OUT OUT OUT OUT OUT OUT OUT
IN
IN
IN
IN
IN
IN
480 to 511
IN
OUT OUT OUT OUT OUT OUT OUT OUT
IN
IN
IN
IN
IN
IN
<Example>
If the presetting pattern number is set to ‘5,’ addresses 0 to 255 will be input addresses, and addresses 256 to
511 will be output addresses.
In this case, if the number of I/O control points is set to ‘384,’ addresses 0 to 255 will be input addresses, and
addresses 256 to 383 will be output addresses.
Содержание SL-VGU1-C
Страница 2: ...2 ...
Страница 5: ...5 Before Using This System ...
Страница 11: ...11 Chapter 1 Designing System ...
Страница 20: ...20 Chapter 1 MEMO ...
Страница 21: ...21 Chapter 2 SL VGU1 C Gateway Controller for CC Link ...
Страница 64: ...64 Chapter 2 MEMO ...
Страница 65: ...65 Chapter 3 SL VGU1 D Gateway Controller for Devicenet ...
Страница 94: ...94 Chapter 3 MEMO ...