56
Chapter 2
Construction
Connection of I/O device
Connect input device to the
SL-VT
□
E
,
and connect output device to the
SL-VTP
□
E
. If it is connected
wrong, it may cause brekage.
CAUTION
The I/O device connection method depends on the connection-to unit.
●
To connect an I/O device to the SL-VT□J and SL-VTP□J
1.
Attach the
SL-CP1
,
SL-CP2
, or
SL-CP3
snap male connector to
the cable distributed from the I/O device. (For the hook-up meth-
od, refer to pages 37, 38, and 44, 45.)
Pin No.
Input device
Output device
1
+24V
2
0V
3
Input
No connection
4
No connection
Output
2.
Connect the snap connector to the connector I/O unit.
Insert the snap male connector all the way into the slot.
If the connector is not inserted all the way into the slot, the connector may cause imperfect contact,
and the system may malfunction.
CAUTION
Connector I/O unit
Snap male connector
4-core flat cable
Cable of connected device
7
6
5
4
3
2
1
0
●
To connect an I/O device to the
SL-VT□E
and
SL-VTP□E
●
Connect an e-CON conforming connector (4P type) that is launched
by various manufactures to the cable distributed from the I/O device.
For the instruction of e-CON spec. based connector, contact manu-
factures of e-CON conforming connector.
Pin No.
Input device
Output device
1
+24V
2
N.C.
3
0V
4
Input
Output
Note:
Make sure that the pin configuration is dif
-
ferent between
SL-VT
□
J
and
SL-VT
□
E
.
A
4
3
2
1
0
7
6
5
e-CON conforming connector (4P type)
(Please arrange separately.)
4-core flat cable
e-CON connector
I/O unit
Cable of the connected device
Содержание S-LINK V
Страница 2: ...2 ...
Страница 5: ...5 Before Using This System ...
Страница 12: ...12 Before Using This System MEMO ...
Страница 13: ...13 Chapter 1 Designing System ...
Страница 35: ...35 Chapter 2 Wiring ...
Страница 60: ...60 Chapter 2 MEMO ...
Страница 61: ...61 Chapter 3 Starting System ...
Страница 71: ...71 Chapter 4 Specifications ...
Страница 161: ...161 Chapter 5 Troubleshooting ...
Страница 169: ...169 Appendix ...
Страница 180: ...180 Appendix MEMO ...