17
Chapter 1
Outline of Design
●
The main line is the longest route distributed from the controller or control board.
●
The branch lines are the routes branched from the main line.
NOTE
The total cable length should satisfy the conditions shown in the following table:
Transmission mode
Total cable length (m)
A
100
B
400
C
1,600
The maximum transmission distance (between D and G) is as follows:
●
Mode A: 50m
The maximum length is 50m regardless of the cable conductor cross section (0.3 to 2.0mm
2
) and the number
of nodes (1 to 256 nodes).
●
Mode B
Conductor
cross
section
(mm
2
)
Number of nodes and maximum transmission length (m)
Up to 224 nodes
Up to 256 nodes
0.3
180
0.5
200 (full specification for mode B)
0.75
1.25
2.0
●
Mode C
Conductor
cross
section
(mm
2
)
Number of nodes and maximum transmission length (m)
Up to 32
nodes
Up to 64
nodes
Up to 96
nodes
Up to 128
nodes
Up to 160
nodes
Up to 192
nodes
Up to 224
nodes
Up to 256
nodes
0.3
570
440
350
300
260
220
200
180
0.5
710
580
490
420
370
330
300
0.75
780
670
590
530
480
1.25
800 (full specification for mode C)
2.0
●
Voltage drop b24V and 0V is not considered. For this reason, calculate this volt-
age drop value, and use a local power supply unit, etc. to prevent voltage drop.
For a detailed description, refer to page 23.
● The conductor cross section of the exclusive 4-core flat cable
SL-RCM
□ is 0.5mm
2
.
●
Wire the
S-LINK V
system while observing the communication distance specifications de
-
scribed above. In addition, use the cables that satisfy the specifications described above.
●
To select applicable cables, refer to the section describing cables.
For a detailed description, refer to page 153.
●
The picking switch
SL-VPK0
□ cannot be used in mode A (transmission mode).
NOTE
Outputting Error Signals
If the controller is equipped with the error signal output function, the controller can output an error signal after
detection of an error.
To output an error signal, the
S-LINK V
system will be turned on properly. If an error occurs, the NPN output
transistor will be turned off.
For each type of error, you can select whether the error signal should be output.
For the Troubleshooting, refer to page 166.
For the error, refer to page 170.
Содержание S-LINK V
Страница 2: ...2 ...
Страница 5: ...5 Before Using This System ...
Страница 12: ...12 Before Using This System MEMO ...
Страница 13: ...13 Chapter 1 Designing System ...
Страница 35: ...35 Chapter 2 Wiring ...
Страница 60: ...60 Chapter 2 MEMO ...
Страница 61: ...61 Chapter 3 Starting System ...
Страница 71: ...71 Chapter 4 Specifications ...
Страница 161: ...161 Chapter 5 Troubleshooting ...
Страница 169: ...169 Appendix ...
Страница 180: ...180 Appendix MEMO ...