Specifications
Type
PLC input connector
PLC output connector
Model No.
SL-VS
□
SL-VP
□
Supply voltage
24V DC±10% (Supplied from
SL-VCU1
)
Current consumption
30mA or less
(Excluding current supplied to PLC input module)
73mA or less
(Excluding current supplied to PLC output module)
Connection
Up to 16 connectors can be connected to each
SL-VCU1
Up to 8 connectors can be connected to each control cable
(Use of connector link cable)
Compatible PLC module
Connector number setting
Using switches, in the range of 0 to 15
Number of I/O points
Input: 32 points
Output: 32 points
Indicators
Transmission
Green LED (blinks when the synchronization signal is sent from the
SL-VCU1
)
Input
Green LED×32
-
Output
-
Orange LED×32
Environmental resistance
Ambient temperature
0 to +55°C (No dew condensation) (Note), Storage: -20 to +70°C
Ambient humidity
10 to 90% RH, Storage: 10 to 90% RH
Noise immunity
Power line: 500Vp, 10ms cycle, 1μs pulse width
Common: 1,000Vp, 10ms cycle, 1μs pulse width (with noise simulator)
Voltage withstandability
1,000V AC for one min. between all terminals connected together and enclosure
Insulation resistance
20MΩ, or more, with 500V DC megger between all terminals connected together and enclosure
Vibration resistance
10 to 150Hz frequency, 0.75mm amplitude or maximum acceleration 49m/s² in X, Y and Z directions for two
hours each
Shock resistance
147m/s
2
acceleration (approx. 15G) in X, Y and Z directions for three times each
Mounting
Connector manufactured by Fujitsu Component Ltd.: Mounting screws
MIL connector: Connector with lock function
Tightening torque
Connector manufactured by Fujitsu Component Ltd.: 0.4N·m
Material
Enclosure: Polycarbonate
Weight
Connector manufactured by Fujitsu Ltd.: approx. 45g, MIL connector: approx. 30g
Accessory
Connector cap: 1 pc.
Note: If this product is stored in the control panel together with the other units, the temperature may rise above the specified operation tem
-
perature due to the heat generated by the other units. In this case, install a cooling fan, etc. so that the ambient temperature can be in the
specified range.
Содержание S-LINK V
Страница 2: ...2 ...
Страница 5: ...5 Before Using This System ...
Страница 12: ...12 Before Using This System MEMO ...
Страница 13: ...13 Chapter 1 Designing System ...
Страница 35: ...35 Chapter 2 Wiring ...
Страница 60: ...60 Chapter 2 MEMO ...
Страница 61: ...61 Chapter 3 Starting System ...
Страница 71: ...71 Chapter 4 Specifications ...
Страница 161: ...161 Chapter 5 Troubleshooting ...
Страница 169: ...169 Appendix ...
Страница 180: ...180 Appendix MEMO ...