31
Chapter 1
Transmission Delay Time
System setting time
<Table 6 Time required for system setting>
Number of
I/O control
points
Time required for system setting (ms)
A mode
B mode
C mode
32
142.7
427.0
1593.0
64
235.3
797.4
3074.8
96
342.0
1224.3
4782.3
128
462.8
1707.7
6715.7
160
597.8
2247.5
8874.9
192
746.8
2843.7
11259.8
224
910.0
3496.4
13870.6
256
1087.3
4205.5
16707.1
288
1278.7
4971.1
19769.5
320
1484.2
5793.1
23057.6
352
1703.8
6671.6
26571.5
384
1937.6
7606.5
30311.2
416
2185.4
8597.9
34276.7
448
2447.4
9645.7
38468.0
480
2723.4
10750.0
42885.1
512
3013.6
11910.7
47528.0
<Table 7 Time required for refreshing stop>
Number of
I/O control
points
Time required for refreshing stop (ms)
A mode
B mode
C mode
32
15.7
62.8
251.3
64
37.7
150.9
603.5
96
69.1
276.5
1106.2
128
110.0
439.9
1759.4
160
160.2
640.8
2563.2
192
219.8
879.4
3517.5
224
288.9
1155.6
4622.3
256
367.4
1469.4
5877.7
288
455.2
1820.9
7283.6
320
552.5
2210.0
8840.0
352
659.2
2636.7
10546.9
384
775.3
3101.1
12404.4
416
900.8
3603.1
14412.4
448
1035.7
4142.7
16570.9
480
1180.0
4720.0
18880.0
512
1333.7
5334.9
21339.6
<Table 8 Time required for transmission check>
Number of
I/O control
points
Time required for transmission check (ms)
A mode
B mode
C mode
32
69.5
134.3
422.1
64
82.6
186.8
632.2
96
100.4
258.1
917.5
128
123.0
348.3
1278.1
160
150.2
457.2
1713.9
192
182.2
585.0
2225.0
224
218.8
731.6
2811.4
256
260.2
897.0
3473.0
288
306.2
1081.2
4209.9
320
357.0
1284.3
5022.1
352
412.4
1506.1
5909.5
384
472.6
1746.8
6872.2
416
537.5
2006.3
7910.1
448
607.1
2284.6
9023.4
480
681.3
2581.7
10211.8
512
760.3
2897.6
11475.6
1. Time required for
transition to system
setting mode 3 sec.
3. Refreshing
stop
6. Output
0.5ms
4. Output
0.5ms
Setting of system
(Pressing of button)
Transition to RUN / CHECK mode
(Using mode setting switch)
READY
output
Completion of
communication check
Error output OFF → ON
Canceling of
errors 3 and 4
Indication of number
of nodes of PLC I/O
connector unit: 6.4 sec.
ON
OFF
ON
OFF
S-LINK V
Controller
5. Transmission
check
2. System setting
● READY output in CONFIG mode (RUN
→ CONFIG)
● READY output in CONFIG mode (
CONFIG mode at power-on)
Содержание S-LINK V
Страница 2: ...2 ...
Страница 5: ...5 Before Using This System ...
Страница 12: ...12 Before Using This System MEMO ...
Страница 13: ...13 Chapter 1 Designing System ...
Страница 35: ...35 Chapter 2 Wiring ...
Страница 60: ...60 Chapter 2 MEMO ...
Страница 61: ...61 Chapter 3 Starting System ...
Страница 71: ...71 Chapter 4 Specifications ...
Страница 161: ...161 Chapter 5 Troubleshooting ...
Страница 169: ...169 Appendix ...
Страница 180: ...180 Appendix MEMO ...