76
Chapter 4
Specifications
No.
Designation
Function
1
Power supply terminal
13: F.G.
Su24V, 0V, or F.G. power from the external power supply unit.
14: F.G.
15: 0V
16: +24V
2
Transmission cable
terminal
9: G
Su24V, 0V, D, or G power to the I/O unit.
10: D
11: 0V
12: +24V
3
Hexadecimal number
display mode indicator
(Orange)
Indicates the current display mode of the address display.
• ON: The hexadecimal number display mode is selected.
• OFF: The decimal number display mode is selected.
4
Address display (Red)
The displayed item depends on the mode ('RUN,' 'CHECK,' or 'CONFIG' mode).
Use the mode selector switch to switch the mode.
<RUN mode>
• Each transmission mode (3 modes in total) will be indicated by the following character, and the LED of
each character will sequentially light just like rotating clockwise.
A Mode
B Mode
C Mode
• If an error occurs, the error message will appear.
Note: After eliminating the cause of the error, press ENTER key and SELECT keys (2 types of keys) at
the same time. The error message will disappear.
<CHECK mode>
•
The number of connected nodes will be displayed first. After that, each time SELECT key is pressed,
the recognized addresses will be displayed one after another.
Number of connected nodes:
Using the decimal or hexadecimal number, the number of I/O units and the number of PLC I/O connec-
tors will be displayed.
Address:
Using the decimal or hexadecimal number, the addresses of the I/O units and the PLC I/O connectors
will be displayed sequentially.
Note: In the hexadecimal number display mode, the hexadecimal number indicator (orange) lights up.
<CONFIG mode>
• Settings will be displayed sequentially. To switch the displayed setting, use SELECT key.
• When RUN mode is switched to CONFIG mode, different item will be displayed compared with the dis-
played item just after power-on. For a detailed description, refer to page 66.
5
ENTER key
Press ENTER key to determine the set condition value.
In the system setting mode, press and hold ENTER key for 3 seconds or more, then the system will be
set.
6
SELECT keys
Use these keys to switch the displayed item or set item.
Also use these keys to change the set condition value.
7
Transmission mode
indicator (Green)
This indicator will blink during transmission (when the transmission signal is being output).
The indicator blinking cycle depends on the transmission speed.
8
Error indicator (Red)
This indicator indicates the error status as follows:
• Lights up when an error occurs.
• Blinks when the cause of the error is eliminated.
9
Mode selection switch
Switches the mode (RUN, CHECK, or CONFIG mode).
10
Output terminal
5: Error output 1
Turns off the output transistor if an error occurs.
For each error, you can select error output 1, 2, or no output.
6: Error output 2
7: READY
Turns on the output transistor if the system is ready for transmission.
8: COM. (+24V)
COM. terminal for READY signal output and error outputs 1 and 2
11
PLC connector terminal
1: G
Su24V, 0V, D, or G power to the PLC I/O connector.
2: D
3: 0V
4: +24V
Содержание S-LINK V
Страница 2: ...2 ...
Страница 5: ...5 Before Using This System ...
Страница 12: ...12 Before Using This System MEMO ...
Страница 13: ...13 Chapter 1 Designing System ...
Страница 35: ...35 Chapter 2 Wiring ...
Страница 60: ...60 Chapter 2 MEMO ...
Страница 61: ...61 Chapter 3 Starting System ...
Страница 71: ...71 Chapter 4 Specifications ...
Страница 161: ...161 Chapter 5 Troubleshooting ...
Страница 169: ...169 Appendix ...
Страница 180: ...180 Appendix MEMO ...