137
Chapter 4
Specifications
Output module
(
SL-VMP8
: 8-channel,
SL-VMP16
: 16-channel)
●
Specifications
Type
8-channel
16-channel
Model No.
SL-VMP8
SL-VMP16
Supply voltage
24V DC±10% (Supplied from
S-LINK V
controller or separate power supply)
Current consumption
(24V DC)
60mA or less (Note 1)
95mA or less (Note 1)
Address setting
0 to 511 (Set by pins No. 19 to 28)
Output
NPN open-collector transistor (photo-isolation)
• Maximum sink current: 100mA
• Applied voltage: 30V DC or less (between output and 0V)
• Residual voltage: 1.5V or less (at 100mA sink current)
0.4V or less (at 16mA sink current)
Output operation
The output transistor will be turned on if the output signal is sent from the signal transmission line.
Short-circuit protec-
tion
Incorporated (Note 2)
Number of output points
8 points
16 points
Environmental resistance
Ambient
temperature
-10 to +55°C (No dew condensation or icing allowed), Storage: -20 to +70°C
Ambient humidity
35 to 85% RH, Storage: 35 to 85% RH
Noise immunity
Power line: 500Vp, 10ms cycle, 1µs pulse width
Common: 1,000Vp, 10ms cycle, 1µs pulse width (with noise simulator)
Vibration
resistance
10 to 150Hz frequency, 0.75mm amplitude or maximum acceleration 49m/s² in X, Y and Z directions for two
hours each
Weight
Approx. 15g
Notes: 1) This value does not include the current consumption and the output load current of the connected output machine.
2) If one of the output channels is shorted, the short-circuit protective function will be activated to protect all the channels, and outputting
signals to the external machine will be stopped. Eliminate the cause of the problem, and the system will be automatically restored.
3) The power supply circuit of this product does not have any short-circuit protective function. Adopt a short-circuit protective function,
such as a fuse, for the power supply circuit.
4) In some cases, you cannot install the same
SL-VMP16
units close to each other, or
SL-VMP16
unit and
SL-VM16
unit close to each
other. The distance between these units depends on the ambient temperature.
While referring to the following figure, secure enough distance between the units.
16
4
0
8
12
-
10 0
10 20 30 40 5055
L=20
L=30
L≥40
L
Units
Number of simultaneously turned-on points (point)
Ambient temperature (°C)
Содержание S-LINK V
Страница 2: ...2 ...
Страница 5: ...5 Before Using This System ...
Страница 12: ...12 Before Using This System MEMO ...
Страница 13: ...13 Chapter 1 Designing System ...
Страница 35: ...35 Chapter 2 Wiring ...
Страница 60: ...60 Chapter 2 MEMO ...
Страница 61: ...61 Chapter 3 Starting System ...
Страница 71: ...71 Chapter 4 Specifications ...
Страница 161: ...161 Chapter 5 Troubleshooting ...
Страница 169: ...169 Appendix ...
Страница 180: ...180 Appendix MEMO ...