128
Chapter 4
Specifications
●
Specifications
Designation
Analogue output unit
Model No.
SL-VTDA1
Supply voltage
24V DC±10% (supplied from the
S-LINK V
controller or separate power supply)
Current consumption
90mA or less (excluding connecting device)
Address setting
0 to 511, settable with switch (Note 1)
Resolution
1/4,000 (12 bits)
Total accuracy
Within ±0.8%F.S. (at -10 to +55°C ambient temperature)
Analogue output
Channel No.
1 channel
Output range
Selectable with switch
• Current output: 4 to 20mA
• Voltage output: +1 to +5V
0 to +10V
-10 to +10V
Output allowable
load resistance
Current output: 250Ω or less, Voltage output: 1kΩ or more
Data conversion time
Approx. 1ms (excluding the delay of
S-LINK V
system transmission time)
Occupied output No.
12 points
Power indicator
Green LED (lights up when the power is ON)
Transmission indicator
Green LED (blinks to indicate the synchronization signal transmission from
S-LINK V
controller)
Output holding function
Incorporated
Environmental resistance
Ambient tempera-
ture (Note 2)
-10 to +55°C (No dew condensation or icing allowed), Storage: -20 to +70°C
Ambient humidity
35 to 85% RH, Storage: 35 to 85% RH
Noise immunity
Power line: 500Vp, 10ms cycle, 1µs pulse width
Common : 1,000Vp, 10ms cycle, 1µs pulse width (with noise simulator)
Voltage withstandability
1,000V AC for one min. between all terminals connected together and enclosure
Insulation resistance
20M
Ω
, or more, with 500V DC megger between all terminals connected together and enclosure
Vibration resitance
10 to 150Hz frequency, 0.75mm amplitude or maximum acceleration 49m/s² in X, Y and Z directions for two
hours each
Shock resistance
490m/s
2
acceleration (approx. 50G) in X, Y and Z directions for three times each
Mounting
Mounted on DIN rail or by tightening screws
Tightening torque
Mounting screw: 0.8N·m or less
Material
Enclosure: ABS, Mounting base: POM
Cable
0.5mm
2
4-core flat cable, 0.6m long
Weight
Approx. 100g
Accessory
Analogue output unit mounting base: 1pc.
Notes: 1) The data of the address exceeding I/O control points is invalid.
2) If this product is stored in the control panel together with the other units, the temperature may rise above the specified operation tem
-
perature due to the heat generated by the other units.
In this case, install a cooling fan, etc. so that the ambient temperature can be in the specified range.
Содержание S-LINK V
Страница 2: ...2 ...
Страница 5: ...5 Before Using This System ...
Страница 12: ...12 Before Using This System MEMO ...
Страница 13: ...13 Chapter 1 Designing System ...
Страница 35: ...35 Chapter 2 Wiring ...
Страница 60: ...60 Chapter 2 MEMO ...
Страница 61: ...61 Chapter 3 Starting System ...
Страница 71: ...71 Chapter 4 Specifications ...
Страница 161: ...161 Chapter 5 Troubleshooting ...
Страница 169: ...169 Appendix ...
Страница 180: ...180 Appendix MEMO ...