5.10.1. Selection of recommended fuses
The fuses recommended for use in the fuse protection
functional units are defi ned according to the tests carried
out. The following
table shows the recommended fuse ratings according to
the U
r
/P
transf.
ratio:
U
r
network
[kV]
U
r
cubicle
[kV]
U
r
fuse
[kV]
Rated power of the transformer
WITHOUT OVERLOAD
[kVA]
25
50
75
100 125
160 200 250
315
400
500
630
800
1000 1250 1600 2000
Rated fuse current (A) IEC 60282-1
10
24
6/12
6.3
10
16
16
20
20
25
31.5
40
50
63
63
80
100
160
200
-
13.5
24
10/24
6.3 6.3 10
16
16
20
20
25
31.5
40
50
63
63
80
100
-
-
15
24
10/24
6.3 6.3 10
16
16
16
20
20
25
31.5
40
50
63
80
80
-
-
20
24
10/24
6.3 6.3 6.3
10
16
16
16
20
20
25
31.5
40
50
50
63
80
125
Table 5.1.
Recommended fuse calibres
1.
Fuses recommended: SIBA brand with medium type
striker, conforming to IEC 60282-1 (Low loss fuses).
2.
The values for combined fuses, in accordance with
IEC 62271-105, are greyed.
3.
The fuse-switch assembly has been temperature-rise
tested under normal service conditions according to
IEC 62271-1.
4.
A fuse-holder carriage adapted for 292 mm 6/12 kV
fuses is available.
5.
For ratings not marked in bold the measurement is
442 mm.
6.
If any of the fuses blows, we recommend changing all
three.
7.
For overload conditions in the transformer or use of
other brands of fuse, please check with
Ormazabal
.
For the auxiliary services function, the recommended
fuse is "Back up" type 10/24 kV, 442 mm, calibre 2 A.
Transfer current according to IEC 62271-105:
U
r
fuse
[kV]
U
r
cubicle
[kV]
I
transfer
[A]
12
12
2300
24
24
1600
Table 5.2.
Transfer current
IG-078-EN version 12; 23/04/2020
83
General Instructions
cgmcosmos
: Medium-voltage cubicles with full insulation
in SF
6
gas up to 24 kV in accordance with IEC Standard
Recommended sequence of operations