4.5. Floor fastening
Before assembling the cubicles, the floor must be carefully
levelled to prevent any deformation which may make it
difficult to connect the cubicles to one another.
4.5.1. Floor fastening on profile
If the floor of the facility is not sufficiently uniform, it is
advisable to install the medium-voltage cubicles on an
auxiliary profile, to make it easier to connect. This profile,
which can be supplied to order, must be anchored to the
floor using expansion screws.
a
M10 x 25 bolt
b
66x65 mm profile
c
Anchoring bracket
Figure 4.14.
Fastening of cubicles on profile
IG-078-EN version 12; 23/04/2020
31
General Instructions
cgmcosmos
: Medium-voltage cubicles with full insulation
in SF
6
gas up to 24 kV in accordance with IEC Standard
Installation