5.6.4. Switch-disconnector closing operation from isolating position
1.
Move the black slider in the grey area to the left (this
releases the lever access so the switch-disconnector
can be connected).
2.
Closing operation:
a. Manual operation
(B driving mechanism). Insert
the lever in the switch-disconnector access (grey
area) and turn clockwise 90º.
b. Motorised operation
(BM driving mechanism).
Activate the corresponding operation command.
When, for any reason, the motor stops halfway through
a motorised operation, before restarting it you must
finish the operation manually, so that the whole
mechanism: sensors, controllers, etc. are in a reliable,
effective and logical position for the control system of
the motorised unit when it is switched back on.
Figure 5.28.
Lever turn process
3.
Verify that the cubicle is in closed position.
Figure 5.29.
Switch-disconnector connected
IG-078-EN version 12; 23/04/2020
63
General Instructions
cgmcosmos
: Medium-voltage cubicles with full insulation
in SF
6
gas up to 24 kV in accordance with IEC Standard
Recommended sequence of operations