5.11.4. Closing operation from isolating position
Initial conditions:
Switch-disconnector open,
earthing switch open, springs charged and circuit-
breaker closed.
1.
Open the circuit-breaker by pressing the opening
button and check the status indicator.
Figure 5.74.
Opening button detail
2.
Move the slide in the grey area to the left.
Figure 5.75.
Slide detail and indication of circuit-breaker
IG-078-EN version 12; 23/04/2020
87
General Instructions
cgmcosmos
: Medium-voltage cubicles with full insulation
in SF
6
gas up to 24 kV in accordance with IEC Standard
Recommended sequence of operations