4.8. Cable connections
[10]
It is advisable to use fully insulated connectors for voltages of 24 and 17.5 kV, according to HD 629.
The medium-voltage incoming and outgoing feeders are
linked to the transformer or, occasionally, other cubicles
via cables. These cables and the corresponding bushings
on the
cgmcosmos
system cubicles can be connected with
simple (plug-in) or reinforced (screw-in) connecting points,
either IEC type or IEEE-386 compliant.
The cable compartment contains the connecting cable
bushings for the incoming and outgoing feeders, as well as
for the outgoing feeders to the transformer.
The size of the cable compartment allows the use of both
insulated and partially insulated cable connectors.
[10]
Never touch live connectors, not even screened
connectors. Screening does not constitute a protection
against direct contact.
When the equipment is in service and a reserve cubicle
is left with voltage in the upper busbar and without
the cables in the bottom bushings, insulating plugs
must be placed in the bushings (EUROMOLD type) or
close the earthing switch and lock that position with
a padlock.
The recommended terminations are described below.
Rated
current
[A]
Manufacturer
Connector
12 kV
24 kV
Connector
type
Section
[mm
2
]
Connector
type
Section
[mm
2
]
250
EUROMOLD*
Screened
Angled
158LR
16 - 150
K-158LR
16 – 150
Straight
152SR
16 - 120
K-152SR
25 - 120
3M
Screened
Angled
93-EE-8XX-2
25 - 95
93-EE-8XX-2
25-95
F & G
Screened
Angled
ASW 10/250
25 - 120
ASW 20/250
25 – 120
KABEL-DRAHT
Screened
Angled
SEHDW11
25 - 150
SEHDW21
25 – 250
Straight
SEHDG11
25 - 150
SEHDW21
25 - 150
PFISTERER
Screened
Angled
CAW 20/250
35 - 70
CAW 20/250
35 - 70
PIRELLI
Screened
Angled
PMA-1-250/25
25 - 95
PMA-1-250/25
25 – 95
Straight
PMR-1-250/25
25 - 95
PMR-1-250/25
25 – 95
RAYCHEM
Screened
Angled
RSES
16 – 120
RSES
16 – 120
Straight
RSSS
16 - 95
RSSS
16 – 95
400
3M
Unscreened
93-EE-8XX-2
25 - 95
93-EE-8XX-2
25 - 95
EUROMOLD*
Screened
400LR
70 - 300
K-400LR
25 - 300
400TE
70 - 300
K-400TE
25 – 300
F & G
Screened
AST 10/400
25 - 240
AST 20/400
25 - 240
ASW 10/400
25 – 240
ASW 20/400
25 - 240
ASTS 10/630
120 - 240
ASTS 20/630
25 - 240
Unscreened
AGL 10/630
120 - 240
-
-
AGLS 10/630
120 - 240
-
-
AWK 10/630
25 – 240
ASGS 10/630
25 – 240
AWKS 10/630
25 – 240
AWKS 20/630
25 – 240
KABELDON
Unscreened
KAP 300
10 - 300
-
-
KABEL-DRAHT
Screened
SEHDW12
35 – 185
SEHDW22
25 – 250
SEHDT12
35 – 150
SEHDT22
35 – 150
SEHDW12
35 – 185
SEHDW22
25 - 250
Unscreened
-
25 - 150
SEHDG23
185 - 240
PIRELLI
Screened
PMA-2-400/24
25 – 95
PMA-2-400/24
25 - 95
PMR-2-400/24
50 – 300
PMR-2-400/24
50 – 300
PMA-3-400/24
25 - 240
PMA-3-400/24
25 - 240
RAYCHEM
Unscreened
UHGK+RICS
120 – 300
UHGK+RICS
95 – 240
IXSU+RICS
16 – 800
IXSU+RICS
16 – 800
Continued on next page
IG-078-EN version 12; 23/04/2020
40
Installation
General Instructions
cgmcosmos
: Medium-voltage cubicles with full insulation
in SF
6
gas up to 24 kV in accordance with IEC Standard