6.
Connect the terminals on the bushings (e).
Figure 4.53.
Rear connection in modular cubicles up to 1300 mm high
7.
Adjust the pins to the terminals using the tensioner.
Also secure the cables with the cable support (f).
Figure 4.54.
Rear connection in modular cubicles up to 1300 mm high
8.
Connect the terminal earth braids, if applicable, and the
cable screens.
9.
Put the cable compartment cover back in place.
IG-078-EN version 12; 23/04/2020
47
General Instructions
cgmcosmos
: Medium-voltage cubicles with full insulation
in SF
6
gas up to 24 kV in accordance with IEC Standard
Installation