5.8.6. Earthing operation from open position
1.
Move the yellow slider to the right (this releases the
lever access so the earthing switch can be connected).
2.
Insert the lever in the earthing switch access, move the
actuator arm to the end and turn clockwise 90º.
Figure 5.49.
Lever turn process
3.
Verify that the cubicle is in earthing position.
Figure 5.50.
Earthing switch closed
IG-078-EN version 12; 23/04/2020
74
Recommended sequence of operations
General Instructions
cgmcosmos
: Medium-voltage cubicles with full insulation
in SF
6