2. Handling and transport
[3]
Position the rear of the cubicle facing the driver, to avoid damaging the front.
Important:
During transport, the switchgear must
be perfectly seated and fixed so that it cannot move
about and possibly damage the equipment.
2.1. Lifting means
The switchgear must always be kept upright, directly on the
ground or on a pallet depending on the type of handling
involved.
One of the following methods must be used for assemblies
of up to 4
cgmcosmos
functional units:
1.
Using a forklift truck or pallet truck.
[3]
Figure 2.1.
Lifting a
cgmcosmos
cubicle using a forklift truck
2.
Lifting using slings or chains fixed to the lifting brackets
on the sides of the top of the cubicle. The angle of pull
should be as vertical as possible (with an angle greater
than 60º from the horizontal).
Figure 2.2.
Lifting
cgmcosmos
cubicles with chains
IG-078-EN version 12; 23/04/2020
15
General Instructions
cgmcosmos
: Medium-voltage cubicles with full insulation
in SF
6
gas up to 24 kV in accordance with IEC Standard
Handling and transport
Содержание velatia cgmcosmos
Страница 119: ......