Inspection
−49−
Product
Type
LED status
Alarm
code
Alarm type
System status
Cause
Remedial action
NETC01-M3
RS-485 communication
compatible product
Between
NETC01-M3
and RS-485
communication
compatible product
MECHATROLINK-
Ⅲ
communication error
−
−
Communication between
the
NETC01-M3
and
RS-485 communication
compatible product cannot
be performed.
The RS-485 communication
compatible product corresponding
to the "communication (address
number)" parameter does not exist.
Check the address number of the
RS-485 communication compatible
product.
The communication of the RS-485
communication compatible product
was shut off while communicating.
•
Check the RS-485 communication
cable.
•
Check the power supply of the RS-
485 communication compatible
product.
When the RS-485 communication
cable was connected incompletely
or it was not connected, the power
supply was turned on.
Check the RS-485 communication
cable.
10.2 Warning
If a warning generates, the D_WAR of the command status (CMD_STAT) for the
NETC01-M3
is turned
ON (1).
The motor will continue to operate.
Once the cause of the warning is removed, the warning will automatically cleared and the D_WAR will be
turned OFF (0).
The present warning can be checked using the
OPX-2A
or
MEXE02
. You can also check the records of up
to ten most recent warnings starting from the latest one, or clear the warning records.
Note
The warning records can be cleared by turning off the
NETC01-M3
power.
Warning
code
Warning type
Cause
Remedial action
E4h
RS-485
communication
error
The RS-485 communication
error was detected.
•
Check the transmission rate of RS-485
communication.
•
Check the connector or cable of RS-485
communication.
E5h
RS-485
communication
timeout
Even though the receiving cycle
of RS-485 communication has
passed, the response frame
was not completed receiving.
•
Check the connector or cable of RS-485
communication.
•
Check the power supply of the RS-485
communication compatible product.
11 Inspection
It is recommended that periodic inspections for the items listed below are conducted after each operation
of the motor. If an abnormal condition is noted, discontinue any use and contact your nearest Oriental
Motor sales office.
•
Is any of the
NETC01-M3
DIN rail mounting parts loose?
•
Is any of the connection parts of the
NETC01-M3
loose?
•
Is there attachment of dust, etc., on the
NETC01-M3
?
•
Are there any strange smells or appearances within the
NETC01-M3
?
Note
The
NETC01-M3
uses semiconductor elements. Handle the
NETC01-M3
with care since static
electricity may damage semiconductor elements. Static electricity may damage the
NETC01-M3
.
Содержание NETC01-M3